Automatic functions
Display Corlo Touch KNX
• Status: 09.03.2017 • Technical changes and errors reserved.
Now select the conditions for stopping the frost alarm. Set which outdoor temperature
must be exceeded (e.g. 5.0°C) and for how long (e. g. 5 hrs.). Select a period ensuring
that ice has completely melted away.
You adjust which blinds will be retracted and which windows will be closed in the
automatic functions for the individual blinds and windows.
Heat protection
The heat protection for shades and windows will be active when the outdoor
temperature set here falls below a defined level. Hysteresis determines how many
degrees the outdoor temperature has to fall below the set heat protection temperature
to void the heat protection status.
Automatic Reset
After manual operation, the respective automatic channel always remains in manual
mode, automatic mode is deactivated. At the time of the daily automatic reset, the
channels may be returned to automatic mode. In addition, you may determine that
after a certain period the automatic mode is reactivated.
Automatic resets prevent manual operation of drives which then might remain in an
inconvenient position (window inadvertently remains open, shutter remains retracted
despite sunlight).
Automatic resets may be activated and deactivated separately for each automatic
channel.
Start frost alarm when
an outdoor temperature of ... (in 0.1°C) is
undercut.
-50 ... 40; 20
during or up to ... (in hours) after
precipitation
1 ... 10; 5
End frost alarm when
an outdoor temperature of ... (in 0.1°C)
30 ... 100; 50
for more than ... (in hours) is exceeded
1 ... 10; 5
Temperature (in 0.1°C)
100 ... 500; 350
Hysteresis (in 0.1°C)
10 ... 200; 50
The drives can be reset daily at
Time (Hours)
0 ... 23; 3
Time (minutes)
0 ... 59
or
after (in minutes)
5 ... 480; 60
to automatic after manual operation.