34
System settings via ETS
Display Corlo Touch KNX
• Status: 09.03.2017 • Technical changes and errors reserved.
Before the system can be used, you have to have the basic configuration set up by the
integrator in the KNX software ETC. Afterwards, some system settings may be
modified directly on the display.
2.1.
Basic configuration in the ETS
First, make some basic settings for data transfer.
The integrated brightness sensor of the
Display Corlo Touch KNX
distinguishes
between "day" and "night". This is used, e. g. for adapting the display brightness.
However, the respective object no. 12 may also be transmitted to the bus and used for
setting up AND links (e. g. night AND object in the range of the proximity sensor).
Specify whether the
Display Corlo Touch KNX
should receive the date and time as
one common or as two separate objects. Via object no. 10, the date and the time are
requested from the bus. As soon as the data is available on the bus, the query cycle is
reset, regardless of whether the query was generated autonomously or arrived from
another bus member. The query cycle of several cycles is therefore usually set to the
same value.
For the
Corlo Touch KNX WL
, the device name for the WLAN (Elsner app) can be en-
tered here. The name should be chosen so that you can easily locate and assign the
device to the network.
Transmission delay after power-up and
programming
5 s • ... • 2 h
Maximum message rate
• 1 message per second
• ...
• 10 messages per second
• ...
• 20 messages per second
Object "Room brightness status"
transmitting
Object no. 12
• not
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Date and time are received via
• two separate objects
• one common object
Transmission cycle of the object "Date and
time query" (in s)
Object no. 10
[50...420; 120]
Device name
[free text]