121
Automatic functions
Display Corlo Touch KNX
• Status: 09.03.2017 • Technical changes and errors reserved.
Alternatively, you can use three objects, with one object switching between eco and
standby mode and the two others are used to activate comfort mode or frost/heat
protection mode. The comfort object then blocks the eco/standby object, and frost/heat
protection objects have the highest priority. Objects
"... Mode (1: Eco, 0: Standby)",
"... comfort activation mode" and
"... frost/heat protection activation mode"
Select the mode to be activated after reset (e.g. power failure, reset of the line via the
bus). (Default).
Then configure a block of the temperature control by the blocking object.
Determine when the current settings of the controls are to be transmitted to the bus.
Periodic transmission is safer if a message does not reach a recipient. You may also
set up periodical monitoring by the actuator with this setting.
The status object shows the current status of the output variable (0 = OFF,
>0 = ON) and may, for example, be used for visualisations or to switch off the heating
pump as soon as the heating is off.
Switch mode via
• two 8-bit objects (HVAC modes)
• three 1-bit objects
Mode after reset
• Comfort
• Standby
• Eco
• Building protection
The folllowing modes can be
selcted via the operating surface:
Comfort
Yes • No
Standby
Yes • No
Eco
Yes • No
Building Protection
Yes • No
Behaviour of the blocking object at value
• 1 = block | 0 = release
• 0 = block | 1 = release
Blocking object value
before 1st communication
0 • 1
Send actuating variables
• on change
• on change and periodically
from change of (in % absolut)
0...10; 2
cycle
for periodical transmission only
5 s • ... • 5 min • … • 2 h
Send status objects
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically