100
Automatic functions
Display Corlo Touch KNX
• Status: 09.03.2017 • Technical changes and errors reserved.
Twilight
The twilight threshold value denominates the brightness point when the system
determines it to be "night". Please note that a brightness value of almost 10 Lux may
be reached in moonlit nights. If the twilight threshold value is set to under 10 Lux,
shades that are supposed to "close at night" might remain open because of the
moonlight, or actually open because of it.
Travel delays
Travel delays prevent the solar protection system from continuously extending and
retracting in the event of rapid changes in lighting conditions.
The brightness must remain uninterrupted above the aperture value set for solar
protection for a set "extension delay time" (e. g. 1 minute) before the shade will extend.
If the light intensity is below the threshold value for the duration of the "retraction
delay short" without interruption, the set reaction for "short" is activated, e. g. the slats
are opened. Only if the light intensity is uninterruptedly under the threshold value for
the duration of the "retraction delay long", the shade is retracted.
Windows opening limitation
The opening limitation determines that a window only opens partly when the outdoor
temperature is low. This prevents excessive cooling of the room.
Set the temperature here below which windows should only be opened within limits.
Then also decide for how long this temperature setting has to be exceeded in order to
deactivate the opening limitation.
The degree to which the opening should be limited is set within the automation
functions for the different windows.
Lock time duration for automatic mode
after wind alarm in minutes
0 ... 360
below (in Lux)
night settings are activated
(switch delay = 1 minute)
1 ... 200; 10
Extension delay for blinds in minutes
1 ... 240; 1
Short retraction delay for shades in
minutes
1 ... 240; 5
Long retraction delay for shades in minutes
1 ... 240; 30
Start if below ...
(in 0.1°C)
-50 ... 150; 20
End if temperature exceeded for more than
(in hours)
1 ... 72; 8