INSTRUCTION MANUAL

BARGRAPH INDICATING ALARM

(with 2-wire transmitter excitation)

MODEL

48NAVD

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Bargraph indicator (incl. scale plate) .................................(1)
Mounting bracket ................................................................(2)
Bezel*

1

..................................................................................(2)

Watertight packing .............................................................(1)
*1. The size of included bezel differs depending on option code.

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• 

This equipment is suitable for Pollution Degree 2 and In-
stallation Category II (transient voltage 2500V).  Rein-
forced insulation (signal input to output to power input: 
300V) is maintained.  Prior to installation, check that the 
insulation class of this unit satisfies the system require-
ments.

• 

The equipment must be mounted on a panel surface.  
Once mounted on a panel, take appropriate precautions 
to prevent operators to be exposed to the terminal block.

• 

Altitude up to 2000 meters.

• 

Insert a noise filter for the power source connected to the 
unit.  TDK-Lambda Noise Filter Model RSAN-2006 or 
equivalent is recommended.

• 

The equipment must be installed such that appropriate 
clearance and creepage distances are maintained to con-
form to CE requirements.  Failure to observe these re-
quirements may invalidate the CE conformance.

• 

The actual installation environments such as panel con-
figurations, connected devices, connected wires, may affect 
the protection level of this unit when it is integrated in a 
panel system.  The user may have to review the CE re-
quirements in regard to the whole system and employ ad-
ditional protective measures to ensure the CE conformity.

• 

In order to enable the operator to turn off the power in-
put immediately, install a switch or a circuit breaker ac-
cording to the relevant requirements in IEC 60947-2 and 
properly indicate it.

 

POWER INPUT RATING & OPERATIONAL RANGE

• 

Locate the power input rating marked on the product and 
confirm its operational range as indicated below:

  100 – 240V and 85 – 264V AC rating: 85 – 264V, 50/60 Hz, 
     

 

approx. 5.5 – 8.5VA

  24V DC rating: 24V ±15%, approx. 3 – 3.5W

 

GENERAL PRECAUTIONS

• 

Before you remove the unit or mount it, turn off the power 
supply and input signal for safety.

• 

Be sure to put the terminal cover on while the power is 
supplied. 

 

ENVIRONMENT

• 

Indoor use.

• 

If the unit’s environmental protection is compromised 
(e.g. when multiple units are to be mounted side by side) 
when heavy dust or metal particles are present in the air, 
install them inside an enclosure with a proper ventilation.

• 

Do not install the unit where it is subjected to continuous 
vibration.  Do not subject the unit to physical impact.

• 

Environmental temperature must be within -10 to +55°C     
(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

REQUIREMENTS TO ENSURE IP65

• 

Observe the designated panel cutout size (31.5 

×

 138 mm).

• 

Single mounting only.  IP65 is not ensured when the units 
are clustered side by side.

• 

The watertight packing included in the product package 
must be placed behind the front cover.

• 

The mounting bracket must be fastened tightly until they 
hit the panel.

• 

Confirm visually that the packing is not contorted or ex-
cessively run off the edge after installation.

 

WIRING

• 

Do not install cables close to noise sources (relay drive 
cable, high frequency line, etc.).

• 

Do not bind these cables together with those in which 
noises are present.  Do not install them in the same duct.

 

TERMINAL BLOCK

• 

The terminal block is separable in two pieces.  Loosen two 
screws on top and bottom of the terminal block to separate.

• 

Be sure to turn off the power supply, input signal and 
power supply to the output relays before separating the 
terminal block.

Terminal Block

Separable

Terminal Block Screw
(top & bottom)

 

AND ....

• 

The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

Summary of Contents for 48NAVD

Page 1: ...conformity In order to enable the operator to turn off the power in put immediately install a switch or a circuit breaker ac cording to the relevant requirements in IEC 60947 2 and properly indicate it POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 100 240V and 85 264V AC rating 85 264V 50 60 Hz approx 5...

Page 2: ...ve at the minimum of 3 cm above and below the units for heat dissipation Note 2 No bezel is needed when the panel is cut according to the above drawings Panel thickness 1 6 8 0 mm Panel thickness 1 6 8 0 mm Vertical Mounting Horizontal Mounting SINGLE MOUNTING Conform to degree of protection IP65 138 1 0 138 1 0 L 138 1 0 164 min L Panel thickness 1 6 8 0 mm L 31 5 36 N 1 N number of units Panel t...

Page 3: ... mm Slide the top and bottom parts of the bezel into the back of the front cover as shown below Bezel When multiple units are to be clustered side by side insert one bezel between two units as shown below When mounting two or more indicators side by side HOW TO MOUNT THE UNIT ON A PANEL 1 Insert the unit into the panel cutout The watertight packing must be in place to hold the unit Do not remove i...

Page 4: ...2 13 14 15 16 16 M3 SCREW TERMINALS Rounded corners for the option D 2 M3 SCREWS 144 5 67 137 5 5 41 4 1 16 36 1 42 OPTION D BEZEL 3 1 Space required when replacing the scale plate 2 Used for the existing panel cutout of M System 48 Series 38 139 5 mm 3 Used for the existing DIN panel cutout 33 138 mm 4 Used for the existing panel cutout of Fuji Electric PAJ PAK PBA 44 138 mm etc STANDARD BEZEL 2 ...

Page 5: ...UT H OUTPUT LL OUTPUT L OUTPUT ALARM OUTPUT CODE 2 2 points ALARM OUTPUT CODE 4 4 points 2 WIRE XMTR MONITOR 1 5V DC V 2 WIRE XMTR MONITOR 1 5V DC V 4 20mA Input without Excitation INPUT 3 2 4 1 250Ω U V POWER U V La Lb Lc Hc Ha Hb H OUTPUT L OUTPUT POWER 1 2 3 4 1 2 3 4 WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 6 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue ter...

Page 6: ...or amber Zero Adj amber L Setpoint Adj Trip Indicator green UP Button Mode Selector DOWN Button H Setpoint L Setpoint PV Indicator M 50 40 30 20 10 0 10 20 30 40 50 m3 h 100 SET L Z S 90 80 70 60 50 40 30 20 10 0 H M Vertical Mounting Horizontal Mounting 50 40 30 20 10 0 10 20 30 40 50 m3 h 100 SET H S Z L 90 80 70 60 50 40 30 20 10 0 SET ENTER Button HH Setpoint Adj Trip Indicator red H Setpoint ...

Page 7: ...e LED OFF LED Blinking Mode Selector 1 S SET S M Span Adjustment Complete SPAN ADJUSTMENT Apply 100 input signal before adjustment ALARM SETTING Proceed after the zero span adjustments 1 Keep pressing at least for 3 seconds to activate Mode Selector M Press briefly for second and more times within 1 minute after it has been activated 2 HH or LL setpoints are not provided for the 48NAVD 2 Note Each...

Page 8: ... after it has been used to choose a indicator LED programming mode During this period pressing the M button briefly is enough to choose another indicator After 1 minute it turns to deactivated state CALIBRATION PROCEDURE This unit is calibrated at the factory to meet the ordered specifications therefore you usually do not need any cali bration For matching the indication to a receiving instrument ...

Reviews: