1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 41 of 149
dP02=15
sanitary water temperature 2
San2
dP02=16
solar panel water temperature
SoLE
dP02=17
temperature probe of the condenser
Cdt1
circuit 1
Cdt2
circuit 2
dP02=18
pressure probe of the condenser 4÷20mA - 0.5V
Cdt1
circuit 1
Cdt2
circuit 2
dP02=19
pressure probe of the evaporator 4÷20mA - 0.5V
LP1
circuit 1
LP2
circuit 2
dP02=20
pressure probe of the compressor oil differential
OIL1
comp 1
OIL2
comp 2
dP02=21
Clock
Forced read - out of the top and bottom display
To force the display read-out:
1. Set the
dP03
parameter not equal to
0
2. Select the value range 1..3
These configurations allow to show together two temperatures or two pressures of the same circuit in order
to have an easier reading of the measurements:
Par.
dP03 = 1
Top display: for both the circuits 1,2:
Evaporator water inlet, with the
Ein
label.
Bottom display: circuit 1:
Evaporator 1 water outlet, with the label
OuT1
Bottom display: circuit 2:
Evaporator 2 water outlet, with the label
OuT2.
Par.
dP03 = 2
Top display of the circuit 1:
Condenser 1 water inlet temperature with the label
CIn1
Bottom display of the circuit 1
Condenser 1water outlet with the label
COu1.
Top display of the circuit 2:
Condenser 2 water inlet temperature with the label
Cin2
Bottom display of the circuit 2
Condenser 2water outlet with the label
Cou2
.
Par.
dP03 = 3
Top display of the circuit 1:
Condenser probe temperature
Cdt1
/ pressure
CdP1
Bottom display of the circuit 1
Evaporator pressure probe
LP1
Top display of the circuit 2:
Condenser probe temperature
Cdt2
/ pressure
CdP2
Bottom display of the circuit 2
Evaporator pressure probe
LP2
Default display read - out of the remote panels VI620S
If the parameter dP04 = 0 the upper display of the remote panels #1 and #2 depends on the parameter
values dP01 – dP02 – dP03; to show the temperature detected by the internal probe of the remote panel
accessing the function menu under the function trEm.
If the parameter dP04 = 1 the upper display of the remote panels #1 and #2 show their internal NTC sensor
(ambient temperature); to show the same temperature it is possible to eccess the function menu under the
function trEm.
15. DISPLAY INFORMATION
Show the Set Point value