1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 103 of 149
ATTENTION
With air/water or water/water units and CF01=1,2 the minimum number of events per hour is 1.
AL17
Active flow input duration
Within this time the flow alarm must be active and after AL17 is expired the alarm is signalled. The counter
starts after AL15 and allows to filter the improvise flow reduction or the possible bubbles of air.
AL18
Not active flow input duration
Within this time the flow alarm must be not active and, after this time, the previous alarm is automatically
reset (if automatic) or, if manual, the unit can be restarted.
ACFL: condenser flow alarm (differential Pressure switch)
Label on alarm
visualization menu
ACFL
condenser flow alarm
Origin
Digital input active for the time set in AL55 after the water pump is on and, after
the digital input itself is activated, for the time set in AL57.
Alarm not enable if AL14=0
Alarm enabled in chiller only if AL14=1
Alarm enabled in heat pump only if AL14=2
Alarm enabled in chiller and heat pump if AL14=3
Reset
Digital input not active for the time AL58.
Restart
Automatic – Manual after AL56 (Reset procedure in Menu function).
Symbol
On the display the symbol
is blinking
Action
Alarm Relay + and buzzer on only during normal running conditions.
Loads
OFF
APFL: solar panel flow alarm
Label on alarm
visualization menu
APFL solar panel flow alarm
Origin
The flow switch alarm is not detecded for AL69 seconds starting from water
pump activation.
Flow switch alarm is signalled if the digital input is active for AL71 seconds.
Reset
Automatic reset: digital input not active for AL72 seconds.
Manual reset: Reset procedure in Menu function
Type of alarm
Automatic if flow switch digital input activation < AL70 + AL71
Manual if Automatic if flow switch digital input activation > AL70 + AL71
Symbol
On the display the symbol
is blinking
Action
Alarm Relay + and buzzer on only during normal running conditions.
Loads
Solar panel water pump OFF
AHFL: sanitary water flow alarm
Label on alarm
visualization menu
AHFL sanitary water flow alarm
Origin
The flow switch alarm is not detecded for AL65 seconds starting from water
pump activation.
Flow switch alarm is signalled if the digital input is active for AL67 seconds.
Reset
Automatic reset: digital input not active for AL68 seconds.
Manual reset: Reset procedure in Menu function
Type of alarm
Automatic if flow switch digital input activation < AL66 + AL67
Manual if Automatic if flow switch digital input activation > AL66 + AL67
Symbol
On the display the symbol
is blinking
Action
Alarm Relay + and buzzer on only during normal running conditions.
Loads
Sanitary water pump OFF
AtSF: Overload alarm of the supply fan