1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 147 of 149
53. ELECTRICAL CONNECTIONS
The instrument is provided with:
3 removable terminal blocks MOLEX with 0.5 mm
2
wires: 16 / 8 /22 ways for digital / analogue inputs and
modulating outputs
4 removable screw terminal block STELVIO for 2.5 mm
2
wires connection: 3 / 4 / 5 / 6 ways for the relay
outputs.
5 ways connector for TTL RS485 interface outputs.
3 ways connector for keyboard VGI890 (to be connected with cable
CABC3J30
The
LW30 KIT
is the complete kit with MOLEX + 3 mt wires already connected and the STELVIO terminals.
Check the connecitons and the line voltage before turning on the power supply.
Keep low voltage cables far from power cables and terminals to prevent.
Respect the maximum load current of each relay output, in case of power loads use filtered contactors.
54. ACCESSORIES
Monophase fan control: 230vac and cut phase control
Models
XV05PK
XV10PK
XV22PK
Power
500W
1000W
2200W
Ampere
2A
4A
9.5A
Scheme
1
1
1