1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 46 of 149
Enter the function Menu
1. Within the Hour function select, with UP or DOWN, the interested label: CO1H, CO2H, CO3H, CO4H,
CO6H, EP1H, EP2H, CP1H, CP2H.
2. Push the
SET
keys for 3seconds: the top display shows the running hours blinking value, then it shows 0
to confirm the reset. The next load label is automatically loaded.
To exit the Hour function push MENU key or wait the timeout
Read-out of the compressor starts-up
For each compressor is possible to show the number of starts-up.
COSn FUNCTION:
number of starts-up of the compressor
Label involved in COSn function:
C1S
number of compressor 1 starts-up ..
C6S
number of compressor 6
starts-up
The labels are displayed only if the corresponding output is present and configured
The number of starts-up is displayed on the top display, the resolution is x 10 (eg 2 means 20 starts, 20
means 200starts)
Enter the function Menu
1. Use the UP or DOWN keys to select
COSn
.
2. Push
SET
one time: the label of the first load C1S is showed on the top display, the bottom display
shows the number x10.
3. With UP or DOWN scroll the compressor list.
4. To exit the Hour function push MENU key or wait the timeout
Reset the starts-up number
Enter the function Menu
1. Within the Hour function select, with UP or DOWN, the interested label: CS1, CS2, CS3, CS4, CS6.
2. Push the
SET
keys for 3seconds: the top display shows the running hours blinking value, then it shows 0
to confirm the reset. The next load label is automatically loaded.
3. To exit the Hour function push MENU key or wait the timeout.
Read-out of the Proportional Output percentage of the condenser fan control
The proportional outputs of the two circuits, that control the fan speed, can be showed in the menu function.
Cond FUNCTION
selects the proportional output 1 and 2.
Label involved in Cond function.
Cnd1
Proportional output status of the condenser fan of the circuit 1.
Cnd2
Proportional output status of the condenser fan of the circuit 2.
TO SEE THE OUTPUT PERCENTAGE:
Enter the function menu
1. Use the UP or DOWN keys to select
Cond
.
2. Push
SET
key: the bottom display shows Cnd1, the top display shows the output percentage.
3. Use the UP or DOWN keys to select Cnd1 or Cnd2, the top display always shows the value, between
0% and 100%, of the proportional output of the selected circuit.
4. To exit the Hour function push MENU key or wait the timeout.
Read-out of the four proportional output
The four proportional outputs, 4..20ma or 0-10V, can be showed in the menu function.
Pout FUNCTION
selects the proportional outputs.
Label involved in Cond function:
Pou1
Proportional output for dumper control or to drive the external relay 1
Pou2
Proportional output for dumper control or to drive the external relay 2
Pou3
Proportional output for dumper control or to drive the external relay 3
Pou4
Proportional output for dumper control or to drive the external relay 4
The labels are displayed only if the corresponding output is present and configured.
TO SEE THE FOUR OUTPUT PERCENTAGE:
Enter the function menu
1. Use the UP or DOWN keys to select
Pout
.
2. Push
SET
key: the bottom display shows Pou1, the top display shows the output percentage.
3. Use the UP or DOWN keys to select Pou1, Pou2, Pou3 or Pou4 the top display always shows the value,
between 0% and 100%, of the proportional output of the selected circuit.
4. To exit the Hour function push MENU key or wait the timeout.
ATTENTION: