1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 71 of 149
CO 90
Condenser water pump ON time
0
250
10 Sec
34. HOT START
In the air air unit and in heating mode it is possible to stop the supply fan when the outlet evaporator
temperature falls below FA24 degrees.
FA24
Hot start Setpoint
FA25
Hot start differential
35. LOAD MAINTENANCE
It is possible to determine for each load (compressors and water pumps) the number of working hours after
witch the display will show a maintenance warning.
Parameters
CO26..CO31:
number of working hour of the compressors
Parameters
CO32..CO33:
number of working hour of the evaporator water pump
Parameters
CO34..CO35:
number of working hour of the condenser water pump
Parameters
CO73:
number of working hour of the sanitary water pump
Parameters
CO74:
number of working hour of the solar panel water pump
Parameters
CO95:
number of working hour of the free cooling water pump
If the parameter is set to 0, the maintenance signalling is disabled but the running hours counter remains
active.
36. CONDENSER FAN REGULATION
The signal to drive the modulating condenser fan is available in the PWM outputs (TF1 and TF2 in the
connection diagram) or in the Out 1 and Out2; for these output the parameters that allows to choose the
signal are:
CF68 Condenser fan circuit 1
CF68=0
0..10V
CF68=1
4..20mA
CF68=2
PWM
CF69 Condenser fan circuit 2
CF69=0
0..10V
CF69=1
4..20mA
CF69=2
PWM