1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 16 of 149
-
dAy:
day of the month (0÷31)
-
MntH:
month (1÷12)
-
yEAr:
year (00÷99)
6. WIRING CONNECTIONS
Ichill 260L
10 relays
18 digital inputs (free of voltage)
10 analogue inputs: NTC probes or through configuration 6 NTC / PTC and 4 pressure transducer 4÷20mA
or ratio-metric 0÷ 5.0Volt
6 modulating outputs
1 output for remote panel (max 2 remote panels)
1 TTL output for “Hot Key 64” connection or for XJ485, interface module for monitoring system, connection.
MAX current on the relay contacts relè 5(2)A 250V - MAX common current 12A 250V
Ichill 261L
14 relays
18 digital inputs (free of voltage)
10 analogue inputs: NTC probes or through configuration 6 NTC / PTC and 4 pressure transducer 4÷20mA
or ratio-metric 0÷ 5.0Volt
6 modulating outputs
1 output for remote panel (max 2 remote panels)
1 TTL output for “Hot Key 64” connection or for XJ485, interface module for monitoring system, connection.
MAX current on the relay contacts relè 5(2)A 250V - MAX common current 12A 250V