Regulation
Compressor
OFF
Other loads
Not modified
C1HP - C2HP - C3HP - C4HP - C5HP - C6HP compressor high pressure alarms
Label on alarm
visualization menu
C1HP
( compressor high pressure alarm 1) – …
C6HP
(compressor high
pressure alarm 6)
Origin
The unit is running and the digital input of the compressor high pressure switch
is active
Reset
Digital input not active
Restart
Reset procedure in Menu function
Reset procedure in Menu function
Always manual AL54 = 0
Always automatic AL54 =16
From manual to utomatic if AL54 value is between 1 and 15
Symbol
On the display the symbol
is blinking
Action
Alarm Relay + and buzzer on
Regulation
Condensing fan
If FA02=0 the fan is forced at maximum speed for 60 seconds then switched
off
If FA02=1 the fan is forced at maximum speed for 60 seconds then regulate
according to normal fan regulation
C1oP - C2oP - C3oP - C4oP - C5oP - C6oP - Pressure switch alarm / compressor oil
Label on alarm
visualization menu
C1oP
(Compressor pressure switch #1) …
C6oP
(Compressor pressure switch
#6)
Origin
The alarm is not signalled: during the AL01 delay after turning on the
compressor, during the AL12 delay that starts after the AL11 delay when the
unit is properly running
Reset
Digital input not active
Restart
Automatic - Manual after AL013 events per hour (Reset procedure in Menu
function).
If AL76=1 the alarm is only a warning and the compressor remains on
Symbol
On the display the symbol
is blinking
Action
Alarm Relay + and buzzer on
OIL ALARM FROM PRESSOSTAT SWITCH OR OIL LEVEL SWITCH (screw)
Occasionally it is possible to find both the safety systems, the delay, the active input duration and the
number of events per hour allow to set-up both the protections.
Par.
AL11
Oil
alarm delay after on compressor.
It allows to set a time delay before signalling the oil or the oil level switch alarms after the on compressor.
Par.
AL12
Duration of the pressure switch / oil level switch in normal operating conditions.
Duration of the oil level switch activation during normal running condition.
It allows to set the time delay before signalling the alarm.
AL11
defines the delay counting, it helps to
override the low pressure or the low oil level determined, for example, by a new partialization step of the
compressor itself.
Par.
AL13
Maximum number of alarm events per hour.
It determs the maximum number of alarm events before switching the restart from automatic to manual.
C1Pd - C2Pd – compressor oil differential pressure
Label on alarm
visualization menu
C1Pd (compressor 1)
C2Pd (compressor 2)