1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 129 of 149
Sd 29
Summer temperature differential relay AUX2
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 30
Winter temperature differential relay AUX2
-30.0
-54
30.0
54
°C
°F
Dec
int
Energy saving
Parameters
Description
min
max
udm
Risoluzione
ES 1
Start of the Time band 1 (0÷24)
0
24.00
Hr
10 Min
ES 2
End of the Time Band 1 (0÷24)
0
24.00
Hr
10 Min
ES 3
Start of the Time band 2 (0÷24)
0
24.00
Hr
10 Min
ES 4
End of the Time Band 2 (0÷24)
0
24.00
Hr
10 Min
ES 5
Start of the Time band 3 (0÷24)
0
24.00
Hr
10 Min
ES 6
End of the Time Band 3 (0÷24)
0
24.00
Hr
10 Min
ES 7
Monday: energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 8
Tuesday energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 9
Wednesday energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 10
Thursday energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 11
Friday energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 12
Saturday energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 13
Sunday energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 14
Energy Saving setpoint offset in chiller mode
-30.0
-54
30.0
54
°C
°F
Dec
int
ES 15
Energy Saving differential in chiller mode
0.0
0
25.0
45
°C
°F
Dec
int
ES 16
Energy Saving setpoint offset in heat pump mode
-30.0
-54
30.0
54
°C
°F
Dec
int
ES 17
Energy Saving differential in heat pump mode
0.0
0
25.0
45
°C
°F
Dec
int
ES 18
Maximum ON time when the unit is switched on by keyboard starting from OFF state
by RTC
0= Not enabled
1
250
Min
10 Min
ES 19
Start of the Time band 1 Sanitary water (0÷24)
0
24.00
Hr
10 Min
ES 20
End of the Time band 1 Sanitary water (0÷24)
0
24.00
Hr
10 Min
ES 21
Start of the Time band 2 Sanitary water (0÷24)
0
24.00
Hr
10 Min
ES 22
End of the Time band 2 Sanitary water (0÷24)
0
24.00
Hr
10 Min
ES 23
Start of the Time band 3 Sanitary water (0÷24)
0
24.00
Hr
10 Min
ES 24
End of the Time band 3 Sanitary water (0÷24)
0
24.00
Hr
10 Min
ES 25
Monday: Sanitary water 2
nd
set point activation
0
7
ES 26
Tuesday: Sanitary water 2
nd
set point activation
0
7
ES 27
Wednesday: Sanitary water 2
nd
set point activation
0
7
ES 28
Thursday: Sanitary water 2
nd
set point activation
0
7
ES 29
Friday: Sanitary water 2nd set point activation
0
7
ES 30
Saturday: Sanitary water 2nd set point activation
0
7
ES 31
Sunday: Sanitary water 2 set point activation
0
7
ES 32
2nd set point Sanitary water offset
-30.0
-54
30.0
54
°C
°F
Dec
int
ES 33
2nd set point Sanitary water differential
0.1
0
25.0
45
°C
°F
Dec
int
Compressors rack
Cr1
Type of functioning compressor rack
0= Not enabled
1= regulation by ST09 probe
2 = regolation by pressure probe (Evaporator pressure probe)
0
2
Cr2
Set point compressor suction probe
Cr03
Cr04
Bar
Psi
Dec
int
Cr3
Minimum set point compressor suction probe
0
Cr03
Bar
Psi
Dec
int
Cr4
Maximum set point compressor suction probe
Cr03
50
725
Bar
Psi
Dec
int
Cr5
Regulation band suction probe
0.1
1
14.0
203
Bar
Psi
Dec
int
Cr6
Set energy saving compressor rack
0.0
0
50.0
725
Bar
psi
Dec
int
Cr7
Differential energy savingcompressor rack
0.1
1
14.0
203
Bar
Psi
Dec
int
Cr8
Number of compressors enabled in case of failure probe
0 ÷ 6
0
6
Cr9
Number od ventilation step in case of failure probe
0 ÷ 4
0
4
Compressors
Parameters
Description
min
max
udm
Risoluzione
CO 1
Minimum compressor ON time after the start-up.
0
250
10 sec
10 sec
CO 2
Minimum compressor OFF time after the switching off.
0
250
10 sec
10 sec
CO 3
ON delay time between two compressors or compressor and valve. During this time
the led of the next resource is blinking.
1
250
Sec