1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 119 of 149
Origin
Pump running hours > Hour counter setpoint
Reset
Hour reset in function menu
Restart
Manual
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Regulation
Action
Only display warning messages
Loads
Not changed
ASAn Sanitary water pump mintenance
Label on alarm
visualization menu
ASAn
(Sanitary water pump maintenance)
Origin
Pump running hours > Hour counter setpoint
Reset
Hour reset in function menu
Restart
Manual
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Regulation
Action
Only display warning messages
Loads
Not changed
ASUn Solar panel water pump mintenance
Label on alarm
visualization menu
ASUn
(Sanitary water pump maintenance)
Origin
Pump running hours > Hour counter setpoint
Reset
Hour reset in function menu
Restart
Manual
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Regulation
Action
Only display warning messages
Loads
Not changed
Alarm relay and buzzer
Alarm relay / buzzer outputs
Origin
Alarms still active
Alarms not reset
Reset relay alarm
Whitout alarms
In stand- by or remote ON-O FF if AL42 = 1
Buzzer silencing
By pushing one of the key of the front panel
The alarm relay is enabled only by configurating the corresponding output resource.
Keyaboard Alarm
Label on alarm
visualization menu
keyaboard Alarm description
noL
No data communication between the keyaboard
and the regulator.