1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 72 of 149
FA01
and
FA02
parameters define the operative mode of the condenser fans.
Par.
FA01
Fan regulation
0 = Output not enabled
1 = Always on
2 = ON/OFF step regulation
3 = ON/OFF continuous step regulation
4 = proportional fan speed
Par.
FA02
Condenser fan operation mode
0 = Fan on only if compressor on
1 = Independent from the compressor and off during the stand–by / or from remote OFF
Example:
Par.
FA01
=
1
/ Par.
FA02 = 0
Fans on when the compressor on (the fans work following the same output algorithm)
Par.
FA01
=
1
/ Par.
FA02 = 1
Independent from the compressor status but off in stand–by.
Par.
FA01
=
2
/ Par.
FA02
=
0
Fans on, with ON/OFF regulation and with temperature/pressure transducer control, only when the
compressor is on (at least one relay is configured as fan control). When the compressor turns off also the
fans are forced off.
Par.
FA01
=
2
/ Par.
FA02
=
1
Fans on, with ON/OFF regulation and with temperature/pressure transducer control, only when the
compressor is on (at least one relay is configured as fan control). When the compressor turns off the fans are
thermoregulated depending on the condensing temperature/pressure.
Par.
FA01
=
3
/ Par.
FA02
=
0
Fans on, with ON/OFF continuos regulation and with temperature/pressure transducer control, only when the
compressor is on (at least one relay is configured as fan control). When the compressor turns off also the
fans are forced off.
Par.
FA01
=
3
/ Par.
FA02
=
1
Fans on, with ON/OFF continuos regulation and with temperature/pressure transducer control, only when the
compressor is on (at least one relay is configured as fan control). When the compressor turns off the fans are
thermoregulated depending on the condensing temperature/pressure.
Par.
FA01
=
4
/ Par.
FA02
=
0
Fans on, with proportional regulation (PWM, 4..20mA, 0.10V) and with temperature/pressure transducer
control, only when the compressor is on. When the compressor turns off also the fans are forced off.
Par.
FA01
=
4
/ Par.
FA02
=
2
Fans on in proportional regulation (PWM, 4..20mA or 0..10V) according to condenser temperature/pressure
(only when the compressor is on).
When the compressor turns off the fans are thermoregulated depending on the condensing
temperature/pressure.
36.1 Output Step Rele’ Condenser Fan
Par FA01 = 2 ON/OFF step regulation
E.G.: 1 circuit and 4 step of ventilation
OUT relè
step n° 1
step n° 2
step n° 3
step n° 4
Out relè step n° 1
ON
OFF
OFF
OFF
Out relè step n° 2
OFF
ON
OFF
OFF
Out relè step n° 3
OFF
OFF
ON
OFF
Out relè step n° 4
OFF
OFF
OFF
ON