1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 27 of 149
10 Temperature probe
NTC
for evaporator outlet 2
11 Temperature probe
NTC
for common evaporator outlet
12 Temperature probe
NTC
for common hot water condenser / recovery inlet
13 Temperature probe
NTC
for hot water condenser / recovery inlet circuit 1
14 Temperature probe
NTC
for hot water condenser / recovery inlet circuit 2
15 Temperature probe
NTC
for hot water condenser / recovery outlet circuit 1
16 Temperature probe
NTC
for hot water condenser / recovery outlet circuit 2
17 Temperature probe
NTC
for hot water condenser / recovery common outlet circuit
18 Temperature probe
NTC
for free cooling water inlet
19 Temperature probe
NTC
for external air dynamic setpoint/ boiler / change over
20 Temperature probe
NTC
for combined defrost circuit 1
21 Temperature probe
NTC
for free cooling water inlet 2
22 Temperature probe
NTC
for auxiliary output 1
23 Temperature probe
NTC
for auxiliary output 2
24 Temperature probe
NTC
sanitary water 1
25 Temperature probe
NTC
sanitary water 2
26 Temperature probe
NTC
solar panel
27 Condenser probe circuit 1 ( temperature
NTC
/ pressure
4÷20 mA
/ ratio-metric
0÷ 5Volt
)
28 Condenser probe circuit 2 ( temperature
NTC
/ pressure
4÷20 mA
/ ratio-metric
0÷ 5Volt
)
29 Evaporator pressure probe circuit 1 (pressure
4÷20 mA
/ ratio-metric
0÷ 5Volt
)
30 Evaporator pressure probe circuit 1 (pressure
4÷20 mA
/ ratio-metric
0÷ 5Volt
)
31 Aux 1 output probe control (
4÷20 mA
/ ratio-metric
0÷ 5Volt)
32 Aux 2 output probe control (
4÷20 mA
/ ratio-metric
0÷ 5Volt)
33 Dynamic setpoint probe (
4÷20 mA)
34 Compressor 1 or circuit 1 pressure probe
35 Compressor 2 or circuit 2 pressure probe
After the number 35 the display read-out goes from “
o 1”
to “
c73
that allows to set an analogue input as
digital input (see polarity input of digital inputs).
Digital Input Configuration Id1 – Id18
Parameters involved:
CF36 =
Configuration ID1…
CF53 =
Configuration ID18
0. Not enabled
1. Remote ON / OFF
2. Remote chiller / heat pump
3. Flow switch/ Supply fan overload
4. Flow switch of heated side
5. Antifreeze heater circuit 1
6. Antifreeze heater circuit 2
7. High pressure switch circuit 1
8. High pressure switch circuit 2
9. Low pressure switch circuit 1
10. Low pressure switch circuit 2
11. Compressor 1 high pressure
12. Compressor 2 high pressure
13. Compressor 3 high pressure
14. Compressor 4 high pressure
15. Compressor 5 high pressure
16. Compressor 6 high pressure
17. Compressor 1 overload
18. Compressor 2 overload
19. Compressor 3 overload
20. Compressor 4 overload
21. Compressor 5 overload
22. Compressor 6 overload
23. Condenser fan overload of circuit 1
24. Condenser fan overload of circuit 2
25. Condenser fan overload of circuit 1 and 2 (comun)
26. Water pump overload of evaporator 1
27. Water support pump overload of evaporator
28. Water pump overload of condenser 1
29. Water support pump overload of condenser