1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 110 of 149
Restart
Manual in function menu
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Regulation
Loads
Not changed
Energy saving
Disabled if based on RTC
Unit ON/OFF
Disabled if based on RTC
AEun: Unloading from high temperature of the evaporator water inlet
Label on alarm
visualization menu
AEUn
Unload signalling from evaporator
Origin
During normal running condition when the temperature/pressure of evaporator
water inlet is higher than CO40 setpoint for the CO42 time delay.
Reset
If the water temperature is lower than CO39 –CO41 (differential)
With unloading ON after the CO43 time delay.
Restart
Automatic
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer OFF
AEht: alarm from high temperature of the evaporator water inlet
Label on alarm
visualization menu
AEht
High water temperature evaporator inlet
Origin
During normal running condition when the temperature/pressure of evaporator
water inlet is higher than AL61 setpoint for the AL60 time delay.
Reset
If the water temperature is lower than AL61 – AL62 (differential)
With unit in stand by or remote OFF if alarm reset is automatic
Restart
Reset procedure in Menu function
Always manual AL59 = 0
Always automatic AL59 =16
From manual to utomatic if AL59 value is between 1 and 15
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
REGULATIONS
Compressor
OFF
Other Loads
Not modified