1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 30 of 149
67. Capacity step valve 3 compressor 3
68. By-pass gas valve compressor 3 start
69. Direct start: compressor 4 relay
PW start: PW 1 of the compressor 4
Star-delta start: relay line 1 of the compressor 4
70. PW start: relay PW 2 of the compressor 4
Star-delta start: relay line 1 of the compressor 4
71. Star centre of the Star-delta start of the compressor 4
72. Capacity step valve 1 of the compressor 4
73. Capacity step valve 2 of the compressor 4
74. Capacity step valve 3 of the compressor 4
75. By-pass gas valve compressor 4 start
76. Compressor 5 relay
77. Compressor 6 relay
Condenser proportional control configuration (2 outputs)
Proportional outputs used to configure a proportional output signal to condenser fan control
Parameters involved:
CF68 =
Condenser control configuration for circuit 1
CF69 =
Condenser control configuration for circuit 2
0= 0 ÷ 10Vdc (for external mono or three-phase fan control board)
1= 4÷20mA (for external mono or three-phase fan control board)
2= PWM (only for external mono-phase fan control board with cut phase control)
Proportional output configuration 0 ÷ 10 Vdc (4 outputs)
Parameters involved:
CF70 =
Proportional output 1 configuration
CF71 =
Proportional output 2 configuration
CF72 =
Proportional output 3 configuration
CF73 =
Proportional output 4 configuration
0
Not enabled
1
Modulated evaporator water pump
2
Modulated Free cooling valve
3
not used
4
Auxiliary output 0÷10V n° 1
5
Auxiliary output 0÷10V n° 2
6 Proportional output for modulating compressor 1
7 Proportional output for modulating compressor 2
After the read-out number 4 the display goes from the label “
o 1”
to “
c47
(see input/output polarity), that
allow to configure the output as digital output to control an external relay.