1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 31 of 149
8. PROGRAMMING WITH THE “HOT KEY 64”
Download: how to program an instrument with a programmed “Hot Key”
1.
Turn off the instrument supply
2.
Insert the hot key.
3.
Turn on the power supply.
4.
Immediately the parameters are downloaded.
During the download the regulation is locked and the top display shows the “
doL
” blinking label. At the end of
the download will appear:
“End”
if the programming procedure is completely OK, after 30seconds the regulation starts automatically.
“Err”
if the programming procedure has found an error and the parameter have not been transferred. In this
case turn off and then on the instrument supply to repeat the operation or remove the hot key, with power
supply off, to restart the regulation.
Upload: How to program a “Hot Key” with the parameters of the instrument
1. Turn on the power supply.
2. Insert the hot key.
3.
Enter the function Menu.
4. Select the
UPL
function (on the bottom display).
5.
Push
SET
key and immediately the instrument starts transfer the parameters into the Hot key.
During the upload the regulation is locked and the top display shows the “
UPL
” blinking label. At the end of
the UPLOAD will appear:
“End”
if the programming procedure is completely OK, after 30seconds the regulation starts automatically.
“Err”
if the programming procedure has found an error and the parameter have not been transferred.
Repeat the procedure.
To exit the UPL function push the MENU key or wait the time-out (15 sec).
9. PROGRAMMING USING THE KEYBOARD
Through the instrument keyboard it is possible to enter the programming. In all the three accessible levels
the user can show and modify both value and visibility of the parameters. To ensure an easy navigation
through the different levels the common parameters have been named and grouped under a family name.
The three levels of programming:
Pr1 User level
Pr2 Maintenance level
Pr3 OEM level
Password default values
Password level Pr1 =
1
Password level Pr2 =
2
Password level Pr3 =
3
Under the function Menu (to reset the Alarm Log or the Compressor Overload) the password is 0 (see
parameter AL46)
Each password can be changed, the range is from 0 to 999.
Each parameter has two level: visibility and modify. Therefore it can be configured as follow:
The parameter can be showed and changed.
The parameter can be showed but not changed.
Enter the Pr1 - Pr2 - Pr3 programming levels
Pr1 LEVEL:
Push
SET
+
DOWN
together for 3 seconds, the top display shows the PAS label and the bottom display
shows the Pr1 label. The leds cir1/cir2 are blinking (up and down leds) to inform that you now are in PR1
programming level.
Pr2 LEVEL:
From the Pr1 level push the UP key for 2 seconds and the bottom display will show Pr2. The top display still
shows PAS.
Pr3 LEVEL: