Origin
Only in defrost if DF01 = 1,3 (defrost en temperature/pressure or external
contact): when the defrost ends after the DF05 timeout.
Reset
Stand - by or remote ON-OFF.
Next defrost ends for temperature/pressure.
Restart
Automatic if next defrost ends for temperature/pressure, otherwise manual.
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer OFF
b1Cu – b2Cu Unloading disabled from High condensing temperature / pressure in chiller
Label on alarm
visualization menu
b1CU
(unloading high temperature from condenser of the circuit # 1)
b2CU
(unloading high temperature from condenser of the circuit # 2)
Origin
When the temperature/pressure of condenser probe control is higher then
CO44
Reset
When the temperature/pressure of condenser probe is lower than CO44 –
CO45 (differential)
After unloading is activated and after Par. CO47
Restart
Automatic
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer OFF
b1Cu – b2Cu: Unloading from low condensing temperature / pressure in Heat pump
Label on alarm
visualization menu
b1CU
(unloading message from condenser #1)
b2CU
(unloading message from condenser #2)
Origin
During normal running condition when the temperature/pressure of
evaporator/condenser probe is lower than < CO46 setpoint
Reset
when the temperature/pressure of evaporator/condenser probe value is
higher than CO46 + CO47
After unloading is activated and after Par. CO48
Restart
Automatic
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer OFF
b1rC – b2rC recovery disabled from high condensing temperature/pressure in Chiller
Label on alarm
visualization menu
b1rC
(recovery disabled message from circuit #1)
b2rC
(recovery disabled message from circuit #2)
Origin
In normal running condition when the temperature/pressure probe value is
higher than the set rC06
Reset
When the temperature/pressure probe value is lower than the rC06 –
rC07(differential)
Unloading start after the time delay Par. rC08
Restart
Automatic
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer OFF
b1PH - b2PH: Pump Down stop alarm from pressure switch / Low pressure switch
Label on alarm
visualization menu
b1PH
(Pump down stop alarm of the circuit 1)
b2PH
(Pump down stop alarm of the circuit 2)
Origin
Pressure switch: if CO36 = 1,2,3,4 and ID not active, the pump down stops
because of the timeout CO39.
Transducer: if CO36 = 1,2,3,4 and the set CO37 is not reached: the pump
stops because of the timeout CO39.