![dixell Ichill 260L_D DUO User Manual Download Page 57](http://html.mh-extra.com/html/dixell/ichill-260l_d-duo/ichill-260l_d-duo_user-manual_2510985057.webp)
1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 57 of 149
Out relay
Cap. step 2
OFF
Cap. step 2
ON
Cap. step 2
OFF
Cap. step 2
OFF
Out relay
Cap. step 3
OFF
Cap. step 3
OFF
Cap. step 3
ON
Cap. step 3
OFF
Step control process
Compressor
Cap.
step 1
Cap.
step 2
Cap.
step 3
Power
0 %
25 %
50 %
75 %
100 %
CO06 = 1 direct action
Eg: compressor with 3 capacity step.
Capacity
25%
50%
75%
100%
Compr.
Compressor
ON
Compressor
ON
Compressor
ON
Compressor
ON
Out relay
Cap. step 1
ON
Cap. step 1
ON
Cap. step 1
ON
Cap. step 1
OFF
Out relay
Cap. step 2
OFF
Cap. step 2
ON
Cap. step 2
ON
Cap. step 2
OFF
Out relay
Cap. step 3
OFF
Cap. step 3
OFF
Cap. step 3
ON
Cap. step 3
OFF
Direct action with sequential step
Compressor
Cap.
step 1
Cap.
step 2
Cap.
step 3
Power
0 %
25 %
50 %
75 %
100 %
CO06 = 2 inverse action
Eg: compressor with 3 capacity step.
Capacity
25%
50%
75%
100%
Compr.
Compressor
ON
Compressor
ON
Compressor
ON
Compressor
ON
Out relay
Cap. step 1
ON
Cap. step 1
ON
Cap. step 1
ON
Cap. step 1
OFF
Out relay
Cap. step 2
ON
Cap. step 2
ON
Cap. step 2
OFF
Cap. step 2
OFF
Out relay
Cap. step 3
ON
Cap. step 3
OFF
Cap. step 3
OFF
Cap. step 3
OFF
Inverse action with sequential step
Compressor
Cap.
step 1
Cap.
step 2
Cap.
step 3
Power
0 %
25 %
50 %
75 %
100 %
CO06 = 3 Continuous steps and direct action
Eg: compressor with 3 capacity step.
Capacity
25%
50%
75%
100%
Compr.
compressor
ON
compressor
ON
compressor
ON
compressor
ON
Out relay
Cap. step 3
OFF
Cap. step 3
ON
Cap. step 3
ON
Cap. step 3
ON