1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 73 of 149
Par FA01 = 3
ON/OFF continuous step regulation
E.G.: 1 circuit and 4 step of ventilation
Continuous step regulation
OUT relè
Gradino n° 1
Gradino n° 2
Gradino n° 3
Gradino n° 4
Out relè step n° 1
ON
ON
ON
ON
Out relè step n° 2
OFF
ON
ON
ON
Out relè step n° 3
OFF
OFF
ON
ON
Out relè step n° 4
OFF
OFF
OFF
ON
36.2 Pwm Output For Fan Control
When the condenser fan is switched on it works at maximum speed for FA03 time, then it modulate
according to condenser pressure/temperature or evaporator pressure (heat pump mode).
F04 parameter allows to adapt the signal to the motor (current-voltage phase displacement of a line-powered
ac load).
If FA01=3, when the compressor starts-up and the proportional regulation requires to turn off the fan (cut-
off), if FA14
0 the fan is forced at the minimum speed for the time set in FA14 itself (if FA14=0 the function is
disabled).
36.3 Condensing Unit: Common Or Separate Condenser
FA05
defines the condenser unit
Par.
FA05
type of condenser
FA05=0 Common condenser unit
FA05=1 Separate condenser units
If FA05= 0 the condenser fan of the circuit 1 and circuit 2 works in parallel:
CHILLER mode:
the regulation probe is the probe that has the higher value
HEAT PUMP mode:
the regulation probe is the probe that has the lower value
36.4 Proportional Regulation Of Condenser Fans
Condenser fan in Chiller mode.
Condenser fan in Heat pump mode.