1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 39 of 149
Fig.2
14. DISPLAY CONFIGURATION
The dP family of parameters allows to set a custom display read-out. The user can change the default read-
out (both for instrument and remote terminals) of the measurements depending on the application.
Top Display
Bottom display
Default read - out of the top display
To set the default value displayed on the top display:
1. Set the parameter dP03 = 0, it means configurable;
2. Select the dP01 parameter into the range 0..14 descripted here below:
PARAMETER
VALUE
DESCRIPTION
CORRESPONDING
LABEL
dP01=0
No label
No label
dP01=1
temperature probe of the evaporator water inlet
Ein
dP01=2
temperature probe of the evaporator water outlet 1 and 2
Out1
circuit 1
Out2
circuit 2
dP01=3
temperature probe of the uscita common evaporator water outlet
Eout
dP01=4
temperature probe of the condenser water inlet
CIn1
circuit 1
CIn2
circuit 2
dP01=5
temperature probe of the common condenser water inlet
Cin