1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 105 of 149
AtHS Sanitary heaters overload alarm
Label on alarm
visualization menu
AtHS
(sanitary heaters overload)
Origin
Digital input active
Reset
Digital input not active
Restart
Manual (reset procedure in function menu)
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Loads
Sanitay heaters OFF
Phase sequence alarm
Label on alarm
visualization menu
ALSF
Origin
Digital input active
Reset
Digital input not active
Restart
Automatic
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Loads
OFF
AEE Eeprom alarm
Label on alarm
visualization menu
AEE
Origin
Wrong eeprom data
Reset
-------
Restart
Manual
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Loads
OFF
AFr: Power supply frequency alarm
Label on alarm
visualization menu
AFr
(Line frequency alarm)
Origin
The power supply frequency is not equal to the Par. CF83
Reset
Ferquency control parameter adjusted, disabled CF83 = 2, frequency within
the tolerance
Restart
Automatic
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Loads
OFF
ALC1: Generic alarm with stop regulation
Label on alarm
visualization menu
ALC1: generic alarm from digital input with stop regulation
Origin
Digital input configured as generic alarm with stop regulation active after the
delay in Par. AL43