1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 107 of 149
Label on alarm
visualization menu
ACF1
Heat pump unit without 4-way valve not configured
Wrong configuration of defrost parameters dF22 and dF23)
ACF2
Condensing control without probe configuration.
(one probe per circuit with 2 separate circuits, at least 1 probe for common
cond.)
Fan proportional control algorithm not respected:
FA09 + FA11 + FA12 < FA10
FA12 < FA13
FA07 < FA15 < FA08
Fan proportional control algorithm not respected and pump enabled:
FA18 + FA21 + FA20 < FA19
FA21 < FA22
FA16 < FA23 < FA17
Fan ON - OFF regulation algorithm not respected:
FA09 < FA10
Fan ON - OFF regulation algorithm not respected and pump enabled:
FA18 < FA19
With pump and defrost enabled there are no evaporating/condensing
probes.
With triac regulation (CF68, CF69 = 2) the power supply configuration is
Vcc (CF83 = 0)
ACF3
Two digital / analogue inputs configured with the same function or without
the necessary resources (es. compressor 3 overload but compressor 3
relay not configured)
ACF4
CF79 = 1 and none digital input configured as Chiller request or Heat
Pump request
CF79 = 2 and none probe configured as external temperature probe
Unit configured as Heat pump and rack compressorr unit enabled (Cr01
≠0)
CF03 = 1 and wrong configuration of the digital input or digital output for
condensing unit unit
ACF5
Circuito # 2 not configured but at least one of its resources are present (relay:
solenoid pump-down, heaters, inversion valve, fan condensing ON - OFF,
recovery, auxilairy)