1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 116 of 149
Origin
Pistons compressor:
Compressor oil pressure – evaporating pressure < AL78
Screw compressor:
Condensing pressure – compressor oil pressure > AL78
Reset
Pistons compressor:
Compressor oil pressure – evaporating pressure > AL78 + AL79
Screw compressor:
Condensing pressure – compressor oil pressure < AL78 - AL79
Restart
Automatic – Manual after AL80 events per hour (Reset procedure in Menu
function).
Symbol
On the display the symbol
is blinking
Action
Alarm Relay and buzzer on
Compressor / circuit involved OFF
If more than one compressor is configured in the circuressors are OFF
C1dt - C2dt - C3dt - C4dt - C5dt - C6dt High compressor discharge temperature alarm
Label on alarm
visualization menu
C1dt
(High discharge temperature of the compressor #1) -…
C6dt
(High
discharge temperature of the compressor #6)
Origin
The compressor discharge temperature is higher than AL39 setpoint.
ATTENTION
The display resolution is 0.1°C until the read-out is 99.9, over 100°C it is 1°C.
Reset
If the probe value of the high discharge temperature is lower than “AL39 -
AL40 (differential)”
Restart
Automatic. Manual when there are AL41 per hour (Reset procedure in Menu
function).
Symbol
On the display the symbol
is blinking
Action
Alarm Relay and buzzer on
Compressor involved
OFF
C1tr - C2tr - C3tr - C4tr - C5tr - C6tr Compressor overload alarm
Label on alarm
visualization menu
C1tr (Compressor 1 overload alarm) -…C6tr (Compressor 6 overload alarm)
Origin
With active digital input.
The alarm is not detected within the AL19 time delay after the on compressor
Reset
When the digital input is not active
Restart
AL77=0:
Manual reset in Alrm menu if AL20=1
16
Manual reset in cOtr menu; if AL20=0 or number of alarm per hour =
AL20, password is requested
AL77=1:
Automatic reset if the nummer of alarm per hour < AL20 or if AL20=16
Manual reset in Alrm menu if the nummer of alarm per hour = AL20
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Compressor involved
OFF if AL47=0 or AL47=1
Compressor not involved
OFF if AL47=1
b1dF – b2dF Defrost alarm
Label on alarm
visualization menu
b1dF
(Defrost alarm of the circuit #1)
b2dF
(Defrost alarm of the circuit #2)