1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 127 of 149
CF 69
Circuit 2 output signal:
0= 0 – 10V
1= 4 ÷ 20Ma
2= PWM for mono phase fan control board
0
2
Proportional output
CF 70
Proportional output “out 3”
0= Not enabled
1= Modulated evaporator water pump
2= Modulated Free cooling valve
3= Not used
4= Auxiliary output 0÷10V n° 1
5= Auxiliary output 0÷10V n° 2
6= Proportional output for inverter compressor 1 (circuit1)
7= Proportional output for inverter compressor 2 (circuit 2)
Relay driver ON / OFF
0
o 1
7
C47
CF 71
Proportional output “out 4”
0= Not enabled
1= Modulated evaporator water pump
2= Modulated Free cooling valve
3= Not used
4= Auxiliary output 0÷10V n° 1
5= Auxiliary output 0÷10V n° 2
6= Proportional output for inverter compressor 1 (circuit1)
7= Proportional output for inverter compressor 2 (circuit 2)
Relay driver ON / OFF
0
o 1
7
C47
CF 72
Proportional output “out 5”
0= Not enabled
1= Modulated evaporator water pump
2= Modulated Free cooling valve
3= Not used
4= Auxiliary output 0÷10V n° 1
5= Auxiliary output 0÷10V n° 2
6= Proportional output for inverter compressor 1 (circuit1)
7= Proportional output for inverter compressor 2 (circuit 2)
Relay driver ON / OFF
0
o 1
7
C47
CF 73
Proportional output “out 6”
0= Not enabled
1= Modulated evaporator water pump
2= Modulated Free cooling valve
3= Not used
4= Auxiliary output 0÷10V n° 1
5= Auxiliary output 0÷10V n° 2
6= Proportional output for inverter compressor 1 (circuit1)
7= Proportional output for inverter compressor 2 (circuit 2)
Relay driver ON / OFF
0
o 1
7
C47
Remote keyboard
CF 74
Remote keyboard 1 configuration
0= Not enabled
1= Enabled model with ambient temperature sensor
2= Enabled model without ambient temperature sensor
0
2
CF 75
Remote Panel 2 configuration
0= Not enabled
1= Enabled model with ambient temperature sensor
2= Enabled model without ambient temperature sensor
0
2
CF 76
Offset of the probe of the remote terminal 1
-12.0
-10
12.0
53
°C
°F
Dec
int
CF 77
Offset of the probe of the remote terminal 2
-12.0
-10
12.0
53
°C
°F
Dec
int
Icon function
CF 78
Icon function
0=
chiller /
heat pump
1=
chiller /
heat pump
0
1
Chiller / heat pump selection mode
CF 79
0= Chiller / Heat pump selection by keyboard
1= Chiller / Heat pump selection by digital input
2= Chiller / Heat pump selection by analogue input
0
2
Automatic Change over
CF 80
Automatic change over setpoint for chiller/ heat pump selection (CF79 = 2)
-30.0
-22
70.0
158
°C
°F
Dec
int
CF 81
Automatic change over differential (CF79 = 2)
0
0
25.0
45
°C
°F
Dec
int
Unit of measurement
CF 82
°C or °F selection
0= °C / °BAR
1= °F / °psi
0
1
Supply voltage frequency
CF 83
Power supply frequency
0= 50 Hz
1= 60 Hz
2= Vcc power supply
(ATTENTION
When CF83 = 2 the proportional outputs for fan control are not enabled and the
frequency alarm is inhibited)
0
2
Serial Address