1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 98 of 149
Low temperature protection
If the temperature detected by probe selected with FS62 parameter is lower than FS63 set point, the free
cooling is disabled.
The free cooling will be enabled when temperature detected by probe selected with FS62 parameter is
higher than FS63 + FS64.
44.1 FAN SPEED CONTROL IF COMPRESSORS AND FREE COOLING ARE USED
FOR COOLING (CF97=3)
When the free cooling is not active the condenser fan speed is managed like standard regulation.
If free cooling is active:
outside temperature > FS43 + FS44: condenser fan speed is forced at maximum speed
outside temperature < FS43: when outside temperature decreases below FS43 temperature, after
FS45 minutes the condenser fan speed is managed as standard regulation
45. RECOVERY FUNCTION
The recovery function is Enabled if:
1 Par.
rC01
not equal to 0.
2 Chiller running mode.
3 The condensing temperature / pressure is lower than set rC06 –rC07 (differential).
4 The input/output resources are configured
5 The remote recovery digital input is activated.
The recovery function is NOT Enabled if:
1 Par.
rC01
= 0.
2 Heat pump running mode, remote OFF or stand by.
3 The condensing temperature / pressure is higher than set rC06.
4 The input/output resources are not properly configured (alarm ACF9).
5 The remote recovery digital input is not activated.
NECESSARY RESOURCE FOR THE RECOVERY OF THE CIRCUIT #1
Output relay configured as valve for recovery circuit #1.
Remote recovery digital input for circuit #1.
Condenser probe of the circuit #1.
NECESSARY RESOURCE FOR THE RECOVERY OF THE CIRCUIT #2
Output relay configured as valve for recovery circuit #2.
Remote recovery digital input for circuit #2
Condenser probe of the circuit #2.
45.1 UNIT WITH TWO SEPARATE IDRAULIC CIRCUITS
FUNCTIONING
Par.
rC01
= 1 unit with two separate circuits:
CIRCUIT # 1