1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 62 of 149
CO81
Maximum speed of the inverter compressors in sanitary water
1
100
%
CO82
Outside temperature to reduce inverter compressor speed in
Heat pump
-
50.0
-58
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
CO83
Hysteresis temperature to reduce inverter compressor speed in
Heat pump
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
CO84
Compressor speed if outside temperature > CO82
0
100
%
24.1 Inverter Compressor In Heat Pump And External Temperature
It is possible to reduce the compressor speed (both compressor in parallel if configured) in heat pump when
external temperature increases over a determined temperature.
25. COMPRESSOR RACK
The IC200L can manage a compressor rack; the configuration parameters are Cr01…Cr09.
In this operation mode the controller can manage maximum 6 compressors in only one circuit; only the chiller
mode is enabled and the regulation is only in proportional mode.
The parameter Cr01 allows to enable the compressor rack regulation:
Cr01 = 0
Compressor rack regulation disabled
Cr01 = 1
Compressor rack enabled and regulation on the probe defined by parameter ST09
Cr01 = 2
Compressor rack enabled and regulation on the evaporator trasducer
It is possible to choose the number of compressors the controller can use in case of regulation faulty probe;
the parameter involved is Cr08.
It is possible to choose the number of condenser fan steps the controller can use in case of faulty probe; the
parameter involved is Cr09.
The Energy Saving function, in case of compressor rack unit, has dedicated set point and differential
(parameter Cr06 = “Energy saving offset for compressor rack unit”, Cr07 = “Energy saving differential for
compressor rack unit”)
Graph of the compressors thermoregulation