26. COMPRESSORS WITH DIFFERENT CAPACITY
The function is enabled if:
one circuit unit
at least 2 compressor are configured
the capacity of the compressors is not 0 and different for each one
Parameters involved:
CF87
Compressor 1 capacity
0
100%
CF88
Compressor 2 capacity
0
100%
CF89
Compressor 3 capacity
0
100%
CF90
Compressor 4 capacity
0
100%
CF91
Compressor 5 capacity
0
100%
CF92
Compressor 6 capacity
0
100%
CF93
Maximum number of start up of the compressor in 15 minutes
0= Not enabled
0
15
Example:
circuit with 2 compressors:
step 1: the first compressor to be activated is the compressor with lower weight
step 2: the compressor is switched off and is activated the compressor with higher weight
step 3: both compressors are activated
The regulation is a steps; if two compressors with different weight are configured, are available 3 steps
activated in regulation band ST07 or ST08.
ATTENTION:
It is possible to protect the compressor setting a maximum number of activation per hour.