1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 139 of 149
dF 39
Outside temperature differential of the Defrost dinamic set point
-50.0
-54
30.0
54
°C
°F
Dec
int
Heat recovery
Parameters
Description
min
max
m. u.
Resolution
rC 1
Sanitary water regulation mode
0
2
rC 2
Recovery modes
0 = not enabled
1 = 2 indipendent circuit
2 = both the circuit in parallel
0
2
rC 3
Delay time delay with step forced off
0
250
Sec
rC 4
Delay time delay with step forced off after the recovery valve activation
0
250
Sec
rC 5
Recovery minimum time
0
250
Min
rC 6
Minimum interval time between the end and the beginning of the next recovery
0
250
Min
rC 7
Temperature setpoint to disable the recovery
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
rC 8
Temperature differential to restore the recovery
0.1
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
rC 9
Maximum time with recovery disabled (if temperature/pressure within rC6-rC7)
0
250
Min
Sanitary water
Parameters
Description
min
max
m. u.
Resolution
FS 1
Sanitary water regulation mode
0= not enabled
1=valves in water circuit
2=valves in gas circuit
0
2
FS 2
Sanitary water thermoregulation priority
0 = heating / cooling
1 = sanitary water
2 = sanitary water by digital input
0
2
FS 3
Sanitary water thermoregulation set point
FS05
FS06
°C/°F
dec/int
FS 4
Sanitary water thermoregulation band
0.1
0
25.0
45
°C
°F
Dec
int
FS 5
Minimum value of the sanitary water set point
-30.0
-22
FS06
°C
°F
Dec
int
FS 6
Maximum value of the sanitary water set point
FS05
70.0
158
°C
°F
Dec
int
FS 7
Full loads enabling to reach the sanitary water set point
0
1
FS 8
Heaters enabling during the sanitary water thermoregulation
0= not enabled
1= compr heaters
2= only heaters
3= only compressors
0
3
FS 9
Operation working time to activate the heaters during the sanitary water
thermoregulation
0
250
Min
FS 10
Time delay to activate the sanitary water valve
0
250
sec
int
FS 11
Reversing cycle delay during sanitary water thermoregulation
0
250
sec
int
FS 12
Antilegionella function operating mode
0 = interval time
1= weekly
2= daily
0
2
FS 13
Delay time between two Antilegionella cycles
0
250
Hr
0
FS 14
Antilegionella Set point
FS15
FS16
°C/°F
dec/int
FS 15
Minimum value of the Antilegionella set point
-30.0
-22
FS14
°C
°F
Dec
int
FS 16
Maximum value of the Antilegionella set point
FS14
70.0
158
°C
°F
Dec
int
FS 17
Hour selection for the Antilegionella activation
0
24.00
Hr
10 min
FS 18
Day selection for the Antilegionella activation
0
7
FS 19
Minimum operating working time of the Antilegionella cycle
0
250
min
FS 20
Temperature band for heaters deactivation during Antilegionella cycle
0.1
0
25.0
45
°C
°F
Dec
int
FS 21
Temperature differential to enable the freecooling function
0.1
25.0
45
°C
°F
Dec
int
FS 22
Temperature differential for the free cooling regulation
0.1
0
25.0
45
°C
°F
Dec
int
FS 23
Set point for solar panel activation
FS25
FS26
°C/°F
dec/int
FS 24
Differential value for solar panel deactivation
0.1
0
25.0
45
°C
°F
Dec
int
FS 25
Minimum value of the solar panel set point
-30.0
-22
FS23
°C
°F
Dec
int
FS 26
Maximum value of the solar panel set point
FS23
70.0
158
°C
°F
Dec
int
FS 27
Delay time to activate the sanitary water valve starting from pump activation
0
250
sec
FS 28
Delay time to deactivate the sanitary water pump starting from valve deactivation
0
250
sec
FS 29
Maximum operating working time of the Antilegionella cycle
0
250
min
FS 30
Sanitary water: security set point
-30.0
-22
70.0
158
°C
°F
Dec
int
FS 31
Sanitary water: security differential
0.1
0
25.0
45
°C
°F
Dec
int
FS 32
Sanitary water: minimum interruption time
0
250
min
FS 33
Sanitary water pump operation mode
0
1