AL 29
Maximum number of alarm events anti-freeze, low ambient air temperature or low
outlet air temperature before changing from automatic to manual alarm reset:
Always manual reset if AL29 = 0
Always automatic reset if AL29 = 16
From automatic to manual if AL29 = 1. .15
0
16
AL 30
Anti-freeze alarm configuration in chiller
0= to turn the compressors off when the anti-freeze control probe is lower than AL26
(after the time delay), the display shows the alarm label.
Buzzer and Alarm relay are not activated.
1= to turn the compressors off when the anti-freeze control probe is lower than AL26
(after the time delay), the display shows the alarm label.
Buzzer and Alarm relay are activated.
0
1
Anti-freeze alarm in Heat pump mode
AL 31
Setpoint of the minimum limit in heat pump (va da – 30 °C a AL32)
-30.0
-22
AL33
°C
°F
Dec
int
AL 32
Setpoint of the maximum limit in heat pump (va da AL31 a 70 °C)
AL33
70.0
158
°C
°F
Dec
int
AL 33
Anti-freeze alarm setpoint in heat pump
Setpoint temperature for low anti-freeze alarm, low ambient temperature (air/air), low
temperature air outlet (air/air). (from AL31 to AL32)
AL31
AL32
°C/°F
Dec/int
AL 34
Alarm differential in heat pump. To reset the anti-freeze, low ambient Temperature
(air/air), low temperature air outlet (air/air) alarms.
0
0
25.0
45
°C
°F
Dec
int
AL 35
Anti-freeze alarm delay in HP for low outlet air temperature (air/air)
Attention
If during the Stand-by or remote off there is an anti-freeze alarm event, and the AL35
<>0, starting the heat pump mode, from keyboard or digital input. In this case the anti-
freeze alarm is aborted and the compressor starts for the AL35 time to heat the air or
the water.
After the AL35 time if the antifreeze probe value is still lower than AL33 setpoint, for
maximum AL36 seconds, the unit is stopped and the anti-freeze alarm is generated
again.
0
250
Sec
AL 36
Anti-freeze alarm delay for low air ambient temperature or low outlet air temperature in
heat pump normal condition.
The detected temperature must be lower than AL33 for the time AL36 before giving the
alarm
0
250
Sec
AL 37
Maximum number of anti-freeze alarm events for low air ambient temperature or low
outlet air temperature in heat pump. It sets the alarm reset condition:
Always manual reset AL37 = 0
Always automatic reset AL37 = 16
From automatic to manual reset if AL37 = 1..15
0
16
AL 38
Anti-freeze alarm configuration in heat pump
0= to turn the compressors off when the anti-freeze control probe is lower than AL33
(after the time delay), the display shows the alarm label.
Buzzer and Alarm relay are not activated.
1= to turn the compressors off when the anti-freeze control probe is lower than AL33
(after the time delay), the display shows the alarm label.
Buzzer and Alarm relay are activated.
0
1
Compressor high discharge temperature
AL 39
Compressor high discharge temperature setpoint
0
0
150
302
°C
°F
Dec / int
int
AL 40
Compressor high discharge temperature differential
0
0
25.0
45
°C
°F
Dec
int
AL 41
Number of compressor high discharge temperature events per hour to determine the
alarm reset condition:
Always manual reset if AL41 = 0
Always automatic reset if AL41 =16
From automatic to manual if AL41 = 1..15
0
16
Generic alarm 1
AL 42
Maximum number of generic alarm events (each event stop the regulation) before
turning the alarm from automatic to manual:
Always manual AL42 = 0
Always automatic AL42 =16
From manual to utomatic if AL42 value is between 1 and 15
0
16
AL 43
Generic alarm delay time after the digital input activation
0
250
Sec
AL 44
Generic alarm delay time after the digital input is not activate
0
250
10 sec
10 sec
Alarm relay
AL 45
Enable alarm relay with unit in off or stand – by:
0= Alarm output not enabled
1= Alarm output enabled
0
1
Password reset: Alarm log – Compressor overload
AL 46
Password value to reset the alarm log, the compressor overload alarm and antifreeze
alarm
0
999
AL 47
Thermal alarm of the compressor
0= lock the compressor
1= lock the whole circuit
0
1
AL 48
Thermal alarm when the compressor is OFF
0 = Not enabled
1= Alarm enabled
0
1
Oil alarm in OFF
AL 49
Oil alarm when the compressor is OFF
0 = Not enabled
1= Alarm enabled
0
1
Generic alarm / signal 2