Chapter 6 Control Modes of Operation
|
ASDA-A&A+ Series
Revision April 2009
6-3
Settings:
ASDA-A series:
not used
A
B
C
ASDA-A+ series:
D
A
B
C
not used
•
A: Pulse type
A=0: AB phase pulse (4x)
A=1: CW + CCW pulse
A=2: Pulse + Direction
Other
setting:
Reversed
•
B: Input pulse filter
B=0:
500Kpps
B=1:
200Kpps
B=2:
150Kpps
B=3:
80Kpps
This setting is used to suppress or reduce the chatter caused by the noise, etc. However, if
the instant input pulse filter frequency is over high, the frequency that exceeds the setting
value will be regarded as noise and filtered.
•
C: Logic type
0=Positive Logic
1=Negative Logic
Pulse Type
Forward
Reverse
Forward
Reverse
AB phase pulse
CW + CCW pulse
Pulse + Direction
Input pulse interface
Max. input pulse frequency
Line driver
500Kpps
Open collector
200Kpps
Call 1(800)985-6929 for Sales
deltaacdrives.com
Call 1(800)985-6929 for Sales
deltaacdrives.com