V1101, 3.5
Parameter 5:
Linear Scale Ref. left (Y1)
Range
:
0.00-9999.99
Default
:
25.00
Units
:
mm
Function
Y-axis left side linear scale reference position and parallelism adjustment.
Description
This value is displayed on the screen when the reference on the linear scale is passed. When the
reference marker on the linear scale is passed, a reference impulse is given to the electronics. (To
see left and right side separately switch service row on).
Note
This value must be greater than the mechanical travel distance on the scale from reference point
position to the scale end. This travel distance must also be greater than the mechanical travel of
the cylinder from reference point position to the upper dead point mechanical in the cylinder.
Make sure that when the cylinder is on the mechanical upper dead stop the Y-axis value read-out
is between 5 and 10 mm.
Summary of Contents for DA-65
Page 1: ...Delem V0303 MACHINE PARAMETERS MANUAL DA 65 V7 DA 69 V7 DA 68PL V7 DA on Windows V1...
Page 17: ...Delem V1101 1 6...
Page 55: ...Delem V1101 3 16 Parameter 16 19 Not used...
Page 67: ...Delem V1101 3 28 Parameter 28 Not used...
Page 68: ...Delem V1101 3 29 Parameter 29 Not used...
Page 79: ...Delem V1101 3 40 Parameter 40 41 Not used...
Page 81: ...Delem V1101 3 43 Parameter 43 45 Not used...
Page 89: ...Delem V1101 3 53 Parameter 53 Not used...
Page 94: ...Delem V1101 3 58 Parameter 58 Not used...
Page 96: ...Delem V1101 3 60 Parameter 60 119 Not used...
Page 175: ...Delem V1101 6 5 6 4 Crowning parameters Figure 6 4 a...
Page 197: ...Delem V1101 8 3 8 3 Digital I axis parameters Figure 8 3 a...
Page 207: ...Delem V1101 9 5 Figure 9 2 c Figure 9 2 d...
Page 239: ......