CYCLIC DATA EXCHANGE - STD SIGNALS
58
AMT58...PN
Request set/shift of home position
Bit 12
The preset function is controlled by bits 11 and 12 in this Sensor 1 control word G1_STW
and acknowledged by the bit 12 Set/shift of home position executed in the sensor status
word G1_ZSW. The preset value is 0 by default and can be set by using the Telegram 860
and G1_XIST1_PRESET_VALUE (see "
G1_XIST1_PRESET_VALUE" on page 54
). The preset
function has an absolute and a relative operating mode selectable by means of the bit
11 Home position mode in this Sensor 1 control word G1_STW (0 = absolute; 1 = rela
-
tive). Bit 11 and bit 12 in the Sensor 1 control word G1_STW control the preset function
as described in the table below.
The Preset command automatically saves the calculated internal offset values.
BIT 12 BIT 11
ACTION
0
X
Normal operating mode.
The encoder will make no change in the output value.
1
0
Preset mode absolute
The encoder reads the current position value and calculates an
internal offset value from the preset value G1_XIST1_PRE
-
SET_VALUE and the read position value. The position value is then
shifted with the calculated offset value to get the current position
value equal to the preset value. The encoder acknowledges the pre
-
set by setting the bit 12 Set/shift of home position executed in the
sensor status word G1_ZSW. Now the bit 12 Request set/shift of
home position in the sensor 1 control word G1_STW can be set to
zero by the Master. The encoder will end the preset cycle by clearing
the bit 12 Set/shift of home position executed in the sensor status
word G1_ZSW. The new internal offset value is securely stored in
case of voltage breakdown and uploaded again at each power on.
1
1
Preset mode relative (offset)
The encoder uses the preset value G1_XIST1_PRESET_VALUE as a
relative offset value. In this mode the current position value is
shifted by the value deriving from the preset value.
EXAMPLE
A preset value "1000" is intended to shift the current position value
by 1000 steps in the positive counting direction. So a "real" position
value of "5000" will have the value "6000" after the relative shifting
sequence. The encoder will set the bit 12 Set/shift of home position
executed in the sensor status word G1_ZSW to acknowledge the
execution of the shifting. The bit 12 Request set/shift of home posi
-
tion in the sensor control word G1_STW can now be set to zero by
the Master. The encoder will end the preset cycle by clearing the bit
12 Set/shift of home position executed in the sensor status word
G1_ZSW. The internal offset value will be shifted according to the
transferred preset value. The new offset value is securely stored in
case of voltage breakdown and uploaded again at each power on.
NOTE
Refer to "
G1_XIST1 Preset control" on page 64
and "
Summary of Contents for AMT58 Series
Page 1: ......
Page 8: ......
Page 13: ...AMT58x CB CANopen 5 3 1 3 Fissaggio con flangia codice ST 58 FLNG ...
Page 52: ......
Page 55: ...Subject index ...
Page 62: ...AMT58x PB Profibus 5 3 1 3 Installation using a flange code ST 58 FLNG ...
Page 101: ......
Page 102: ......
Page 109: ......
Page 114: ...AMT58x EC EtherCAT 5 3 1 3 Installation using a flange code ST 58 FLNG ...
Page 166: ......
Page 167: ...AMT58 PN INSTRUCTION MANUAL Absolute Encoders ...
Page 180: ...LIST OF ABBREVIATIONS xiv AMT58 PN ...
Page 221: ...TO TECHNOLOGY OBJECTS INSTRUCTION MANUAL 41 Figure 28 TO encoder enabled ...
Page 231: ...INSTRUCTION MANUAL 51 ...
Page 265: ...NORMAL OPERATION DIAGRAM INSTRUCTION MANUAL 85 NORMAL OPERATION DIAGRAM ...
Page 266: ...ENCODER STATE MACHINE 86 AMT58 PN PRESET DIAGRAM ...
Page 267: ...PARKING SENSOR DIAGRAM INSTRUCTION MANUAL 87 PARKING SENSOR DIAGRAM ...
Page 269: ...ERROR DIAGRAM INSTRUCTION MANUAL 89 Acknowledgment of not acknowledgeable sensor error ...
Page 284: ......
Page 285: ......
Page 287: ......
Page 294: ......
Page 299: ...AMT58x CB CANopen 5 3 1 3 Installation using a flange code ST 58 FLNG ...
Page 335: ......
Page 345: ...AMT58x DN DeviceNET 5 3 1 3 Installation using a flange code ST 58 FLNG ...
Page 380: ...AMT58x DN DeviceNET 40 Default 21h ...
Page 384: ...AMT58x DN DeviceNET 44 Default 00h ...
Page 394: ......
Page 404: ...AMT58x PB Profibus 5 3 1 3 Installation using a flange code ST 58 FLNG ...