Troubleshooting
SiENBE28-901
98
Air Cooled Refrigeration Condensing Unit
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Turn power supply off, and
turn power supply on again.
Return to normal?
YES
NO
The connector of outdoor
unit PCB (A1P) for
electronic expansion valve
is connected.
NO
YES
The coil resistance of
electronic expansion
valve is normal. (Refer
to
∗
1)
NO
YES
External factor other than
malfunction (for example, noise
etc.).
Ensure correct connection.
Replace the electronic expansion
valve coil.
Replace outdoor unit PCB (A1P).
∗
Make measurement of resistance between the connector pins, and then make sure the resistance
falls in the range of 40 to 50
Ω
.
(Orange) 1
(Red) 2
(Yellow) 3
(Black) 4
5
COM[+] (Gray) 6
Measuring points
Judgment criteria
1 - 6
40~50
Ω
2 - 6
3 - 6
4 - 6