Troubleshooting
Air Cooled Refrigeration Condensing Unit
79
6.4
Checking Malfunction Codes of the Condensing Unit
Operate the pushbuttons on the PCB and malfunction codes will be displayed by LEDs.
Setting Modes: 1-14, 15, 16, 20, 21, 22
[Steps]
1. Make sure that the "H1P" LED is OFF.
(If the LED is ON, press the MODE button (BS1) once.)
2. Press the MODE button (BS1) once to enter the "monitor mode".
3. Pressing the RETURN button (BS3) will display the first digit of a malfunction code by LED.
4. Pressing the SET button (BS2) will display the second digit of the malfunction code by LED.
5. Pressing the MODE button (BS1) will go back to the former state.
BS1
MODE
BS2
SET
BS3
RETURN
BS4
TEST
BS5
RESET
LED display
Remote
controller
display
Malfunction contents
Page
referred
(Pressing the BS3 switch once)
(Pressing the BS2 switch once)
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
l h k h h l l l k h
h h h h
E0
STD Compressor Motor Overcurrent/
Lock
P.84
h h l h
E2
Earth Leakage
P.86
h h l l
E3
Actuation of High Pressure Switch
P.88
h l h h
E4
Actuation of Low Pressure Sensor
P.90
h l h l
E5
Inverter Compressor Motor Lock
P.92
h l l l
E7
Malfunction of Outdoor Unit Fan Motor
P.94
l h h l
E9
Malfunction of Electronic Expansion
Valve Coil
P.97
l h k h l h l l k h h h l l
F3
Abnormal Discharge Pipe Temperature
P.99
l h k h l h h l k h
h h h h
H0
Three-sensor Malfunction
P.101
h h l l
H3
Malfunction Related to High Pressure
Switch
P.103
h l l l
H7
Abnormal Outdoor Fan Motor Signal
P.104
l h h l
H9
Malfunction of Outdoor Air Thermistor
P.106
l h k h l l h l k h
h h l h
J2
Current Sensor Malfunction
P.107
h h l l
J3
Malfunction of Discharge Pipe
Thermistor
P.108
h l h l
J5
Malfunction of Suction Pipe Thermistor
P.108
l h h h
J8
Malfunction of Heat Exchanger
Intermediate Inlet Thermistor
P.108
l h h l
J9
Malfunction of Heat Exchanger
Intermediate Outlet Thermistor
P.108
l h l h
JA
Malfunction of High Pressure Sensor
P.110
l l h h
JC
Malfunction of Low Pressure Sensor
P.112
l h k h l l l l k h
h h h l
L1
Faulty Inverter PCB
P.114
h l h h
L4
Malfunction of Inverter Radiating Fin
Temperature Rise
P.115
h l h l
L5
INV Compressor Instantaneous
Overcurrent
P.116
l h h h
L8
INV Compressor Overload
P.118
l h h l
L9
Faulty INV Compressor Startup
P.120
l l h h
LC
Malfunction of Transmission (between
Inverter PCB and Main PCB)
P.122
l h k l h h h l k h
h h h l
P1
Power Supply Voltage Imbalance
P.124
h l h h
P4
Faulty Radiation Fin Thermistor
P.125
l h k l h h h l k h l l h l
PJ
Faulty of Capacity Setting
—
l h k l h h l l k h
h h h l
U1
Reverse Phase / Open Phase
P.126
h h l h
U2
Abnormal Power Supply Voltage
P.127