Description of Functions and Operation
SiENBE28-901
56
Air Cooled Refrigeration Condensing Unit
(10) Low pressure protection control
If the pressure drops below 0.00 MPa, the system will cease operation. After 2 to 10 minutes in
standby, the system will resume operation. For a period of 3 hours after power-up, the system
will continue to check whether the suction stop valve is closed. If the stop valve is seen to be
closed, the system will stop and declare a problem (abnormal stop).
Three hours after the system was turned on, the system will no longer stop due to an
abnormally low pressure.
(The low pressure retry code "E4" will be sent to the AIRNET.)
(11) Overheat protection control
If any of the following conditions is met, the system will cease operation. INV compressors
will resume operation after 2 to 6 minutes in standby, while STD compressors will restart
after 3 to 10 minutes. If a particular compressor repeats this procedure 10 times, "F3" will be
sent to the AIRNET; if it repeats it 15 times, the compressor will stop.
For 5 and 6AY1 models, the compressors will stop and declare a problem (abnormal stop).
For 8, 10, 12, 15, and 20AY1 models, the remaining compressors will perform a backup
operation.
If the following condition is met, the relevant compressor will stop immediately and declare a
problem (abnormal stop).
The discharge gas temperature
≥
150°C.
(12) STD compressor overcurrent protection control
The following condition is met, the system will stop operation. STD compressors will resume
operation after 30 minutes in standby. If a compressor repeats this procedure twice, "E0" will
be sent to the AIRNET. If it repeats it three times, the relevant compressor will stop.
The STD compressor current >14.95A for 2.1 seconds or more.
(13) Earth leakage detection control
1. Detection using a earth leakage detection board
If the high-pressure sensor reading exceeds 3.567 MPa, the earth leakage detector PCB will
be activated. Then the compressor operation will stop and declare a problem (abnormal
stop).
To reset, turn off the power switch (or operation switch) and turn it back on again.
2. Detection during initial power-up
The system will check for earth leakage while the compressor is running for the first 10
seconds after power-up. A compressor will stop abnormally if the power breaker is turned off
or the earth leakage detector PCB is activated during the 10-second period describe above.
If the breaker is turned off, turn the breaker on again. If the same thing happens again,
disable the defective compressor and perform a backup operation using the remaining
compressors.
With the operation switch in OFF, reset the system by turning on the power off and then back
on again.
or
• The discharge gas temperature >120°C for 70 seconds.
• The discharge gas temperature >125°C for 30 seconds.
• The discharge gas temperature >130°C