Troubleshooting
SiENBE28-901
128
Air Cooled Refrigeration Condensing Unit
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check for power supply
voltage. Voltage
between phases: 380 to
415V (Y1)
NO
Onsite causes.
Make proper wire connections
without open phase, erroneous
connections, or erroneous order of
phases.
Power ON
Power OFF
Unbalanced power
supply? (Not more than
2%: Phase voltage of
not more than approx.
5V)
Disconnect the cable from the
compressor, and then check
the compressor for the
insulation resistance.
The insulation resistance
is low. (i.e., not more than
100k
Ω
.)
Disconnect the cable from the
fan, and then check the fan
motor for the insulation
resistance.
The insulation resistance
is low (i.e., not more than
1M
Ω
.)
Check the inverter power
transistor.
Has the power
transistor got faulty?
Check the fan driver power
transistor.
Has the power
transistor got faulty?
A
NO
YES
YES
YES
NO
YES
NO
YES
NO
YES
NO
Onsite causes.
Correct the unbalanced loads to
eliminate the unbalanced state.
Unbalanced voltage will cause
extremely unbalanced current,
thus impairing the service life of or
resulting in the malfunction of the
equipment.
Replace the compressor.
Replace the fan motor.
Replace the fan driver.
Replace the inverter PCB.
I
Observe the conditions of the
PCB.
In the case of a serious failure, a
compressor failure may cause
the failure of the PCB. Even if
the PCB is replaced, it may
cause failure again.
To avoid that, recheck the
compressor for ground and for
any broken wires. Furthermore,
even after the completion of
PCB replacement, check the
compressor.
Replace the fan driver PCB.
I
Observe the conditions of the
PCB.