Field Settings
SiENBE28-901
36
Air Cooled Refrigeration Condensing Unit
b-1. Setting mode 2
The number in the “No.” column represent the number of times to press the SET (BS2) button.
No.
Display of setting items
Display of setting conditions
Setting item
H1P H2P H3P H4P H5P H6P H7P
0
Δ
Tsp: Fine-tuning setting of
evaporation temperature
k h h h h h h
2
Current limitation setting
k h h h h k h
3
Setting of limit value of outdoor fan
taps
k h h h h k k
5
Setting of external low noise
operation
(Tax1, 2 and Tay1, 2 are set by
setting 2-21. )
k h h h k h k
6
AIRNET address
k h h h k k h
7
Setting of night-time low noise
operation (Only connected to
AIRNET)
k h h h k k k
8
Night-time low noise start setting.
It uses it for setting 2-7 and 2-11.
(Only connected to AIRNET)
k h h k h h h
9
Night-time low noise end setting.
It uses it for setting 2-7 and 2-11.
(Only connected to AIRNET)
k h h k h h k
11
Δ
Tsn: Evaporation temperature
correction setting during
operation at night-time
k h h k h k k
21
Setting of external temperature of
outdoor fan tap
It uses it by setting 2-5.
k h h k k h k
40
Setting of high static pressure of
outdoor fan
k h k h h h k
(*1)
Standard setting
High static pressure setting
Model name
LRM(L)EQ6,12,20AY1
LRM(L)EQ5,8,10,15,20AY1
LRM(L)EQ6,12,15,20AY1
LRM(L)EQ5,8,10AY1
Factory set
9
9
8
8
Setting 1
8
10
7
9
Setting 2
7
8
6
7
Setting 3
6
7
5
6
Setting 4
5
6
5
5
Setting 5
5
5
5
5
H1P H2P H3P H4P H5P H6P H7P
Δ
Tsp
0K (Factory set)
k
h
h
h
h
h
h
-1°C
k
h
h
h
h
h
k
-2°C
k
h
h
h
h
k
h
-3°C
k
h
h
h
h
k
k
-4°C
k
h
h
h
k
h
h
-5°C
k
h
h
h
k
h
k
+1°C
k
h
h
h
k
k
h
+2°C
k
h
h
h
k
k
k
+3°C
k
h
h
k
h
h
h
+4°C
k
h
h
k
h
h
k
+5°C
k
h
h
k
h
k
h
LRM(L)EQ
H1P H2P H3P H4P H5P H6P H7P
5,6AY1 8,10,12AY1 15,20AY1
No limitation. (Factory set)
k
h
h
h
h
h
k
10A
20A
36A
k
h
h
h
h
k
h
9A
18A
30A
k
h
h
h
k
h
h
7A
14A
27A
k
h
h
k
h
h
h
H1P H2P H3P H4P H5P H6P H7P
Details
depend on
the
following.(*1)
(Factory set)
k
h
h
h
h
h
k
Setting 1
k
h
h
h
h
k
h
Setting 2
k
h
h
h
k
h
h
Setting 3
k
h
h
k
h
h
h
Setting 4
k
h
k
h
h
h
h
Setting 5
k
k
h
h
h
h
h
H1P H2P H3P H4P H5P H6P H7P
6 (Tamb
≤
Tax1)
7(Tay1<Tamb
≤
Tax2)
9(Tamb<Tay2) (Factory set)
k
h
h
h
h
h
k
5(Tamb
≤
Tax1)
6(Tay1<Tamb
≤
Tax2)
9(Tamb<Tay2)
k
h
h
h
h
k
h
H1P H2P H3P H4P H5P H6P H7P Please give the
address of 1 or
more when you do
the AIRNET.
Binary system for
address(six digits)
(Factory set) 0
k
h
h
h
h
h
h
1
k
h
h
h
h
k
k
~
63
k
h
k
k
k
k
k
Standard
setting
High static
pressure setting
H1P H2P H3P H4P H5P H6P H7P
9
9
k
h
h
h
h
h
k
8
7
k
h
h
h
h
k
h
7
8
k
h
h
h
k
h
h
6
6
k
h
h
k
h
h
h
5
5
k
h
k
h
h
h
h
4
4
k
k
h
h
h
h
h
H1P H2P H3P H4P H5P H6P H7P
21:00 (Factory set)
k
h
h
h
h
h
k
22:00
k
h
h
h
h
k
h
23:00
k
h
h
h
k
h
h
20:00
k
h
h
k
h
h
h
H1P H2P H3P H4P H5P H6P H7P
7:00 (Factory set)
k
h
h
h
h
h
k
8:00
k
h
h
h
h
k
h
9:00
k
h
h
h
k
h
h
6:00
k
h
h
k
h
h
h
As for Factory set, time zone between 2-8 and 2-9 becomes effective for setting.
H1P H2P H3P H4P H5P H6P H7P
+1°C(Factory set)
k
h
h
h
h
h
k
+2°C
k
h
h
h
h
k
h
+3°C
k
h
h
h
k
h
h
0°C
k
h
h
k
h
h
h
Tax1 Tay1 Tax2 Tay2 H1P H2P H3P H4P H5P H6P H7P
26°C 28°C 31°C 33°C
k
h
h
h
h
h
k
20°C 22°C 26°C 28°C
k
h
h
h
h
k
h
27°C 29°C 32°C 34°C
k
h
h
h
k
h
h
H1P H2P H3P H4P H5P H6P H7P
Standard setting
(Factory set)
k
h
h
h
h
h
k
High static
pressure setting
k
h
h
h
h
k
h