5.2
Field Wiring
5.2.1 Procedure for Power Supply Wiring
¢
Procedure for Power Supply Wiring
²
1
Power supply (3
φ
380~415)
2
Branch switch or overcurrent circuit breaker
(earth leakage circuit breaker)
3
Earth wire
4
Power supply terminal block
5
Mount insulation sleeves
6
Fix the power supply wiring for phases L1, L2, L3,
and N, respectively, with the provided clamp (1) to
the resin clamp.
7
Fix the earth wire to the power supply wire (phase
N) with the provided clamp (1).
8
Earth wire
Perform wiring so that the earth wire will not come
in contact with lead wires of the compressor.
Otherwise, noise generated may have a bad
influence on other equipment.
9
Ground terminal
10
• When two wires are connected to a single
terminal, connect them so that the rear sides of
the crimp contacts face each other.
• Also, make sure the thinner wire is on top,
securing the two wires simultaneously to the
resin hook using the accessory clamp (1).
Power circuit, safety device, and cable requirements
A power circuit (see the following table) must be provided for connection of the unit. This
circuit must be protected with the required safety devices, i.e. a main switch, a slow blow
fuse on each phase and an earth leakage circuit breaker.
When using residual current operated circuit breakers, be sure to use a high-speed type
(1 second or less) 200mA rated residual operating current.
Use copper conductors only.
Use insulated wire for the power cord.
Select the power supply cable type and size in accordance with relevant local and national regulations.
Specifications for local wiring are in compliance with IEC60245.
Use wire type H05VV when protected pipes are used.
Use wire type H07RN-F when protected pipes are not used.
Phase and frequency
Voltage
Minimum circuit amp. Recommended fuses
LRMEQ5AY1
LRLEQ5AY1
φ
3, 50Hz
380-415V
12.7A
15A
LRMEQ6AY1
LRLEQ6AY1
φ
3, 50Hz
380-415V
13.6A
15A
LRMEQ8AY1
LRLEQ8AY1
φ
3, 50Hz
380-415V
19.2A
25A
LRMEQ10AY1
LRLEQ10AY1
φ
3, 50Hz
380-415V
21.9A
25A
LRMEQ12AY1
LRLEQ12AY1
φ
3, 50Hz
380-415V
23.9A
25A
LRMEQ15AY1
LRLEQ15AY1
φ
3, 50Hz
380-415V
31.2A
40A
LRMEQ20AY1
LRLEQ20AY1
φ
3, 50Hz
380-415V
34.8A
40A