![Daikin LRLEQ10AY1(E) Service Manual Download Page 50](http://html1.mh-extra.com/html/daikin/lrleq10ay1-e/lrleq10ay1-e_service-manual_502370050.webp)
SiENBE28-901
Description of Functions and Operation
Air Cooled Refrigeration Condensing Unit
49
Conversion table for using the evaporation temperature (set by the dip switches) to determine
its pressure equivalent
DS1
Tsd(Lpm1)
DS1
Tsd(Lpm1)
LRMEQ**
LRLEQ**
LRMEQ**
LRLEQ**
-10°C
(0.47MPa)
-35°C
(0.11MPa)
0°C
(0.69MPa)
-25°C
(0.22MPa)
-20°C
(0.29MPa)
-45°C
(0.03MPa)
5°C
(0.82MPa)
-20°C
(0.29MPa)
-15°C
(0.37MPa)
-40°C
(0.07MPa)
10°C
(0.98MPa)
-5°C
(0.56MPa)
-30°C
(0.16MPa)
ON
OFF
1 2 3 4
Factory set
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4