Troubleshooting
SiENBE28-901
112
Air Cooled Refrigeration Condensing Unit
6.6.16 “
JC
” Malfunction of Low Pressure Sensor
Remote
Controller
Display
JC
Applicable
Models
LRMEQ5~20PY1
LRLEQ5~20PY1
Method of
Malfunction
Detection
Malfunction is detected from pressure detected by low pressure sensor.
Malfunction
Decision
Conditions
When the low pressure sensor is short circuit or open circuit.
(Not less than 1.8MPa, or -0.1MPa and below)
Supposed
Causes
Defect of low pressure sensor
Connection of high pressure sensor with wrong connection
Defect of outdoor unit PCB
Defective connection of low pressure sensor
Piping with wrong connection
Reduction of low pressure when the thermistors (Ti, Tg) are defective.