Troubleshooting
SiENBE28-901
106
Air Cooled Refrigeration Condensing Unit
6.6.12 “
H9
” Malfunction of Outdoor Air Thermistor
Remote
Controller
Display
H9
Applicable
Models
LRMEQ5~20AY1
LRLEQ5~20AY1
Method of
Malfunction
Detection
Malfunction is detected from the temperatures detected by the outdoor air thermistor.
Malfunction
Decision
Conditions
While in operation, the thermistor causes a broken wire or a short circuit in it.
Supposed
Causes
Faulty thermistor
Faulty connection of connector
Faulty outdoor unit PCB (control PCB)
Troubleshooting
*1. For "temperature and resistance characteristics of thermistor", refer to the table shown below.
Temp.(°C)
Resistance
(k
Ω
)
Temp.(°C)
Resistance
(k
Ω
)
0
2
4
6
8
65.8
59.4
53.7
48.6
44.0
30
32
34
36
38
16.1
14.8
13.6
12.5
11.5
10
12
14
16
18
40.0
36.3
33.0
30.1
27.4
40
42
44
46
48
10.6
9.8
9.1
8.4
7.7
20
22
24
26
28
25.0
22.9
20.9
19.1
17.5
50
52
54
56
58
7.2
6.7
6.2
5.7
5.3
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check for connector
connection.
Is the resistance
normal?
YES
NO
Disconnect the thermistor
from the outdoor unit PCB,
and then make resistance
measurement using a
multiple meter.
Is the resistance
normal? (*1)
YES
NO
Properly connect it.
Replace the thermistor.
Replace the outdoor unit
PCB (control PCB).