SiENBE28-901
Test Operation
Air Cooled Refrigeration Condensing Unit
57
5. Test Operation
5.1
Refrigerant Piping
[REFRIGERANT]
This System use R410A refrigerant.
Caution
This unit is already filled with a certain amount of R410A.
Never open liquid and gas shutoff valve until the step Specified in “
5.4. CHECKS AFTER
WORK COMPLETION
”.
The refrigerant R410A requires strict cautions for keeping the system clean, dry and tight.
Read this chapter carefully and follow these procedures correctly.
A.Clean and dry
Foreign materials (including mineral oils such as SUNISO oil or moisture) should be
prevented from getting mixed into the system.
B.Tight
Take care to keep the system tight when installing.
R410A does not contain any chlorine, does not destroy the ozone layer, and does not
reduce the earth’s protection against harmful ultraviolet radiation.
R410A can contribute slightly to the greenhouse effect if it is released.
Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its
liquid state. If the refrigerant is charged in a state of gas, its composition changes and the
system will not work properly.
Be sure to perform refrigerant replenishment. Refer to “
5.4 CHECKS AFTER WORK
COMPLETION
” and the label of instructions on refrigerant replenishment on the cover
surface of the control box,
[Important information regarding the refrigerant used]
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent
gases into the atmosphere.
Refrigerant type : R410A
GWP
(1)
value : 2090
(1)
GWP = global warming potential
Please fill in with indelible ink,
1
the factory refrigerant charge of the product,
2
the additional refrigerant amount charged in the field and
1
+
2
the total refrigerant charge
on the refrigerant charge label supplied with the product.
The filled out label must be adhered in the proximity of the product charging port (e.g. onto the
inside of the service cover).
[DESIGN PRESSURE]
Since design pressure is 3.8MPa or 38bar (for R407C units : 3.3MPa or 33bar), the wall
thickness of pipes should be more carefully selected in accordance with the relevant local and
national regulations.
Contains fluorinated greenhouse gases
covered by the Kyoto Protocol
(2)
(1)
(1)=
(2)=
(1)+(2)=
6
5
4
1
2
3
kg
kg
kg
R410A
1 factory refrigerant charge
of the product : see unit
name plate
2 additional refrigerant
amount charged in the field
3 total refrigerant charge
4 Contains fluorinated
greenhouse gases covered
by the Kyoto Protocol
5 outdoor unit
6 refrigerant cylinder and
manifold for charging