SiENBE28-901
Troubleshooting
Air Cooled Refrigeration Condensing Unit
117
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Power OFF
Is the stop
valve open?
Is the
compressor lead
wire normal?
YES
NO
YES
NO
Are wirings and
wire connections
to the compressor
normal?
YES
NO
The insulation
resistance of the
compressor is
not more than
100k
Ω
NO
YES
There is a
broken wire in
the compressor
coil.
NO
YES
Check4
(P.133)
Is the power
transistor
normal?
YES
NO
When restarting,
the fault recurs.
YES
NO
Power OFF
Replace the inverter
PCB (A3P).
When restarting,
the fault recurs.
YES
NO
Open the stop valve.
Replace the compressor lead wire.
Correct the wirings and wire
connections.
Replace the INV compressor.
Replace the INV compressor.
Replace the inverter PCB (A3P).
Continue the operation.
Factors such as instantaneous
power failure are supposed.
Continue the operation.
Replace the INV compressor.