Troubleshooting
SiENBE28-901
120
Air Cooled Refrigeration Condensing Unit
6.6.21 “
L9
” Faulty INV Compressor Startup
Remote
Controller
Display
L9
Applicable
Models
LRMEQ5~20AY1
LRLEQ5~20AY1
Method of
Malfunction
Detection
Malfunction is detected from the signal waveforms of the compressor.
Malfunction
Decision
Conditions
The compressor startup sequence is not complete.
Supposed
Causes
Failure to open the stop valve
Faulty compressor
Erroneous wire connections to compressor
Large differential pressure prior to compressor startup
Faulty inverter PCB
Slugging of refrigerant
Abrasion of sliding parts caused by wet operation due to faulty secondary equipment
expansion valve
Failure of oil return due to faulty onsite piping work
Liquid return caused by operation signal connection failure
Too frequent on/off operation due to insufficient loading