Test Operation
SiENBE28-901
60
Air Cooled Refrigeration Condensing Unit
5.1.3 Drier Installation
Caution
This product requires that a drier be installed on liquid piping on site.
(Operating the unit without a drier installed may result in equipment failure.)
Select a drier from the following chart:
Install the drier in a horizontal orientation wherever possible.
Install the drier as close to the outdoor unit as possible.
Remove the drier cap immediately before brazing (to prevent absorption of airborne
moisture).
Follow instructions in the drier instruction manual concerning drier brazing.
Repair any burning of drier paint that occurs during drier brazing. Contact the manufacturer
for more information about paint for repair use.
Flow direction is specified for some type of the dryer.
Set the flow direction according to the operation manual of the dryer.
5.1.4 Operation Method of Shutoff Valves
Follow the instructions below when operating each shutoff valve.
Caution
Do not open the shutoff valve until the steps specified in “
5.3.3 Checking of device and
installation conditions
” is completed.
Do not leave the shutoff valve opened without turning the power on, otherwise refrigerant
may be condensed in the compressor and the insulation of the main power supply circuit
may be degraded.
Be sure to use an exclusive tool to handle the shutoff valve. The shutoff valve is not of back
sheet type. Excessive force imposed may break the valve.
Use a charge hose when using the service port.
Make sure that there is no refrigerant gas leakage after the valve cover and cap are securely
tightened.
¢
Tightening torque
²
Check with the following table the sizes of shutoff valves incorporated by each model and the
tightening torque values of the respective shutoff valves.
Shutoff valve sizes
Model
Required dryer core
(recommended type)
LRMEQ5AY1, LRLEQ5AY1
LRMEQ6AY1, LRLEQ6AY1
80g (100% molecular sieve equivalent)
(DML083/DML083S : Danfoss made)
LRMEQ8AY1, LRLEQ8AY1
LRMEQ10AY1, LRLEQ10AY1
LRMEQ12AY1, LRLEQ12AY1
160g (100% molecular sieve equivalent)
(DML163/DML163S : Danfoss made)
LRMEQ15AY1, LRLEQ15AY1
LRMEQ20AY1, LRLEQ20AY1
160g (100% molecular sieve equivalent)
(DML164/DML164S : Danfoss made)
5A type
6A type
8A type
10A type 12A type 15A type 20A type
Liquid side
shutoff valve
φ
9.5
φ
12.7
Gas side
shutoff valve
φ
19.1
φ
25.4
φ
31.8
Service port
Valve cover
Shaft
Hexagon hole
Sealing part