SiENBE28-901
Troubleshooting
Air Cooled Refrigeration Condensing Unit
125
6.6.24 “
P4
” Faulty Radiation Fin Thermistor
Remote
Controller
Display
P4
Applicable
Models
LRMEQ5~20PY1
LRLEQ5~20PY1
Method of
Malfunction
Detection
While the compressor stops running, detect the resistance of the radiation fin thermistor.
Malfunction
Decision
Conditions
The thermistor resistance comes to a value equivalent to an open or a short circuit.
Supposed
Causes
Faulty radiation fin thermistor
Faulty inverter PCB
Faulty INV compressor
Faulty fan motor
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Make measurement of
resistance of the radiation fin
thermistor.
Is the resistance of
the thermistor
normal? (See*1)
The insulation
resistance of the INV
compressor is not more
than 100k
Ω
.
NO
YES
YES
NO
The insulation
resistance of the fan
motor is not more than
1M
Ω
.
YES
NO
Does the fault recur
when turning ON the
power supply?
YES
NO
*1. Refer to the characteristics of radiation fin thermistor (P.106).
Replace the inverter PCB.
Replace the INV compressor.
Replace the fan motor.
Replace the inverter PCB.
Continue the operation.