SiENBE28-901
Troubleshooting
Air Cooled Refrigeration Condensing Unit
141
6.7
Maintenance
1. Procedure for Removal of Parts from Refrigerant System
As the results of checking a malfunction, if the malfunction results from part(s) used in the
refrigerant system, remove the part(s) referring to the procedure for refrigerant recovery
shown below.
∗
If liquid refrigerant was recovered, add refrigeration oil according to the following criteria.
Refrigeration oil brand: Idemitsu DAPHNE FVC68D
Amount to be added: Volume of recovered refrigerant (kg) x 0.05 liter
(Example: If the volume of the refrigerant recovered is 24kg, 24 x 0.05 = 1.2 liter of oil that
should be added.)
Fill port: Liquid stop valve service port
For details about adding oil, see the section that describes the refrigeration oil
procedure.
Location of malfunction
Procedure for maintenance
1
Outdoor unit compressors (M1C, M2C and M3C)
Solenoid valves (for STD1 and STD2)
INV electronic expansion valve
Four way valve
High pressure switches
Refer to Maintenance 1.
2
Main electronic expansion valve
Injection electronic expansion valve
Refer to Maintenance 2.
3
Secondary equipment, such as a showcase
Dryer
Refer to Maintenance 3.
4
High pressure sensor
Low pressure sensor
A check valve allows it to be
removed and replaced without any
refrigerant recovery.